Suppression Behavior Difference Between Compressed Air/Nitrogen Foam over Liquid Fuel Surface Under Constant Radiation Heat Flux

被引:7
|
作者
Tian, Fengyuan
Wang, Kun
Fang, Jun
Shah, Hassan Raza
Lang, Xuqing
Mu, Shanjun
Wang, Jinjun
Wang, Jingwu
机构
[1] State Key Laboratory of Fire Science, University of Science and Technology of China, Anhui, Hefei
[2] Department of Fire Protection Engineering, China Fire and Rescue Institute, Beijing
[3] State Key Laboratory of Safety and Control for Chemicals, SINOPEC Research Institute of Safety Engineering Co., Ltd., Shandong, Qingdao
[4] Hefei Institute for Public Safety Research, Tsinghua University, Anhui, Hefei
基金
中国国家自然科学基金;
关键词
Compressed air foam; Compressed nitrogen foam; Drainage; Evaporation; Mass loss mechanism; Fire-extinguishing performance; FIRE; NITROGEN; DRAINAGE; SOLUBILITY; AIR;
D O I
10.1007/s10694-022-01332-0
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
Compressed air foam (CAF) and compressed nitrogen foam (CNF) have been widely used for storage tank fire suppression, benefiting from their highly effective extinguishing performance. Mass loss rate is an important parameter to evaluate the stability of foam and an important factor to influence the suppression efficiency of foam. In this work, mass loss mechanisms including drainage and evaporation of two types of foams under a fixed radiation source were experimentally studied to reflect the foam fire suppression efficiency. It was observed that the foam drain rate is directly proportional to the foam mass, with a slight relation to the irradiance when irradiance is lower than 20 kW/m(2). Once the irradiance reaches 30 kW/m(2), the drain rate increases significantly. For evaporation, as expected from the established theoretical model, the evaporation rate shows a positive relationship with the irradiance level. However, there is no relationship between foam evaporation rate and the initial foam thickness. Through the experimentally measured evaporation rate, the average foam absorptivity is calculated to be approximately 0.63 +/- 0.07 for both foams at an expansion ratio (ER) of 10. A comparative analysis of mass loss characteristics in the two types of foam was also undertaken. It was found that the two types of foam have distinct drain rates due to their different foam stability caused by the different expanded gas properties. However, they have a similar evaporation rate. In addition, the foam destruction rate and time to ignite the underlying fuel were measured, and a linear relationship between ignition time and initial foam height was found with a slope of 1.7 +/- 0.2. The results demonstrate that CNF has a better fire suppression efficiency, which can be attributed to the better stability of the foam and the nitrogen released by broken bubbles, which inhibits ignition. The work presented here reveals the different functional mechanisms of compressed air/nitrogen foam and presents useful information that could enhance our understanding of the fire suppression effects of fire extinguishing foam.
引用
收藏
页码:1225 / 1243
页数:19