Numerical investigation on the performance, sustainability, and efficiency of the deep borehole heat exchanger system for building heating

被引:0
作者
Chaofan Chen
Haibing Shao
Dmitri Naumov
Yanlong Kong
Kun Tu
Olaf Kolditz
机构
[1] Helmholtz Centre for Environmental Research (UFZ),Applied Environmental Systems Analysis
[2] Dresden University of Technology,Institute of Geology and Geophysics
[3] Freiberg University of Mining and Technology,Department of Environmental Sciences
[4] Chinese Academy of Sciences,undefined
[5] China University of Mining and Technology (Beijing),undefined
[6] University of California,undefined
来源
Geothermal Energy | / 7卷
关键词
Deep borehole heat exchanger system; Performance; Sustainability; Temperature recovery ratio; Coefficient of system performance (CSP);
D O I
暂无
中图分类号
学科分类号
摘要
In densely inhabited urban areas, deep borehole heat exchangers (DBHE) have been proposed to be integrated with the heat pump in order to utilize geothermal energy for building heating purposes. In this work, a comprehensive numerical model was constructed with the OpenGeoSys (OGS) software applying the dual-continuum approach. The model was verified against analytical solution, as well as by comparing with the integrated heat flux distribution. A series of modeling scenarios were designed and simulated in this study to perform the DBHE system analysis and to investigate the influence of pipe materials, grout thermal conductivity, geothermal gradient, soil thermal conductivity, and groundwater flow. It was found that the soil thermal conductivity is the most important parameter for the DBHE system performance. Both thermally enhanced grout and the thermally insulated inner pipe will elevate the outflow temperature of the DBHE. With an elevated geothermal gradient of 0.04 °C m−1, the short-term sustainable specific heat extraction rate imposed on the DBHE can be increased to 150–200 W m−1. The quantification of maximum heat extraction rate was conducted based on the modeling of 30-year-long operation scenarios. With a standard geothermal gradient of 0.03 °C m−1, the extraction rate has to be kept below 125 W m−1 in the long-term operation. To reflect the electricity consumption by circulating pump, the coefficient of system performance (CSP) was proposed in this work to better quantify the system efficiency. With the typical pipe structure and flow rate specified in this study, it is found that the lower limit of the DBHE system is at a CSP value of 3.7. The extended numerical model presented in this study can be applied to the design and optimization of DBHE-coupled ground source heat pump systems.
引用
收藏
相关论文
共 50 条
  • [21] Field test and numerical investigation on the heat transfer characteristics and optimal design of the heat exchangers of a deep borehole ground source heat pump system
    Wang, Zhihua
    Wang, Fenghao
    Liu, Jun
    Ma, Zhenjun
    Han, Ershuai
    Song, Mengjie
    ENERGY CONVERSION AND MANAGEMENT, 2017, 153 : 603 - 615
  • [22] Strategic optimization of borehole heat exchanger field for seasonal geothermal heating and cooling
    Bayer, Peter
    de Paly, Michael
    Beck, Markus
    APPLIED ENERGY, 2014, 136 : 445 - 453
  • [23] Experimental and analytical investigation on pipe sizes for a coaxial borehole heat exchanger
    Gordon, David
    Bolisetti, Tirupati
    Ting, David S-K.
    Reitsma, Stanley
    RENEWABLE ENERGY, 2018, 115 : 946 - 953
  • [24] Numerical study of geothermal district heating from a ground heat exchanger coupled with a heat pump system
    Zhang, Xiong
    APPLIED THERMAL ENGINEERING, 2021, 185
  • [25] Long-term dynamic heat transfer analysis for the borehole spacing planning of multiple deep borehole heat exchanger
    Zhang, Fangfang
    Fang, Liang
    Zhu, Ke
    Yu, Mingzhi
    Cui, Ping
    Zhang, Wenke
    Zhuang, Zhaoyi
    Fang, Zhaohong
    CASE STUDIES IN THERMAL ENGINEERING, 2022, 38
  • [26] Influencing factors analysis for the long-term thermal performance of medium and deep U-type borehole heat exchanger system
    Huang, Shuai
    Li, Jiqin
    Zhu, Ke
    Dong, Jiankai
    Jiang, Yiqiang
    JOURNAL OF BUILDING ENGINEERING, 2023, 68
  • [27] Experimental and Numerical Investigation of Nanofluid Usage in A Plate Heat Exchanger for Performance Improvement
    Sozen, Adnan
    Khanlari, Ataollah
    Ciftci, Erdem
    INTERNATIONAL JOURNAL OF RENEWABLE ENERGY DEVELOPMENT-IJRED, 2019, 8 (01): : 27 - 32
  • [28] Investigation of buoyancy effects on heat transfer between a vertical borehole heat exchanger and the ground
    Sharqawy, Mostafa H.
    Badr, Hassan M.
    Mokheimer, Esmail M.
    GEOTHERMICS, 2013, 48 : 52 - 59
  • [29] Influences of stratified ground thermophysical properties on the performance and thermal response test of deep coaxial borehole heat exchanger
    Li, Zhihu
    Fu, Qiang
    Wang, Changlong
    INTERNATIONAL JOURNAL OF GREEN ENERGY, 2024, 21 (02) : 268 - 282
  • [30] Effects of groundwater flow on thermal response test of deep borehole heat exchanger
    Li, Zhihu
    Wang, Changlong
    Fu, Qiang
    GEOTHERMICS, 2022, 106