A numerical study of cascade refrigeration system using two different refrigerant pairs, namely, R41–R404A and R170–R161 working under the same operating conditions has been presented in this paper. A computer code has been developed in Engineering Equation Solver software using the basic energy and exergy equations of cascade refrigeration system. Values of some of the important input parameters for the analysis have been taken from the literatures to carry out this simulation work. The effect of evaporator temperature on the basic performance parameters, such as COP, compressor power, total exergy destruction, exergetic efficiency has been computed. The analysis of the predicted results shows that for each evaporator temperature, an optimal point exists where the system shows maximum performance. An effective reduction of compressor work and total exergy loss is observed with R170–R161 system than those of the R41–R404A system. This eventually results in higher optimal COP as well as exergetic efficiency for R170–R161 system compared to R41–R404A system.
引用
收藏
页码:723 / 731
页数:8
相关论文
共 50 条
  • [1] Energetic and exergetic performance comparison of cascade refrigeration system using R170-R161 and R41-R404A as refrigerant pairs
    Roy, Ranendra
    Mandal, Bijan Kumar
    HEAT AND MASS TRANSFER, 2019, 55 (03) : 723 - 731
  • [2] Comparative analysis of thermodynamic performance of a cascade refrigeration system for refrigerant couples R41/R404A and R23/R404A
    Sun, Zhili
    Liang, Youcai
    Liu, Shengchun
    Ji, Weichuan
    Zang, Runqing
    Liang, Rongzhen
    Guo, Zhikai
    APPLIED ENERGY, 2016, 184 : 19 - 25
  • [3] Thermoeconomic Optimization of Cascade Refrigeration System using Refrigerant Pair R404A-R508B
    Parekh, A. D.
    Tailor, P. R.
    Sutaria, Nirav
    MECHANICAL AND AEROSPACE ENGINEERING, PTS 1-7, 2012, 110-116 : 677 - 684
  • [4] Performance comparison of ultra-low temperature cascade refrigeration cycles using R717/R170, R717/R41 and R717/R1150 to replace R404A/R23
    Chen, Muqing
    Yang, Qichao
    Shi, Benlin
    Chen, Xiaonan
    Chi, Weikai
    Liu, Guangbin
    Zhao, Yuanyang
    Li, Liansheng
    THERMAL SCIENCE AND ENGINEERING PROGRESS, 2023, 44
  • [5] Comparison of a R744 cascade refrigeration system with R404A and R22 conventional systems for supermarkets
    da Silva, Alessandro
    Bandarra Filho, Enio Pedone
    Pontes Antunes, Arthur Heleno
    APPLIED THERMAL ENGINEERING, 2012, 41 : 30 - 35
  • [6] Exergetic performance assessment of a variable-speed R404a refrigeration system
    Kizilkan, Oender
    Kabul, Ahmet
    Yakut, Ali Kemal
    INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2010, 34 (06) : 463 - 475
  • [7] Numerical simulation of R410a-R23 and R404A-R508B cascade refrigeration system
    Parekh, A.D.
    Tailor, P.R.
    Patel, Tejendra
    World Academy of Science, Engineering and Technology, 2010, 46 : 360 - 364
  • [8] BANANA STORAGE PERFORMANCE IN A REFRIGERATION SYSTEM WITH R404A REFRIGERANT AT DIFFERENT PRESSURES
    Aksut, B.
    Polatci, H.
    LATIN AMERICAN APPLIED RESEARCH, 2023, 53 (02) : 173 - 178
  • [9] EXPERIMENTAL STUDY ON REFRIGERATION SYSTEM 'S PERFORMANCE OF THE REFRIGERATOR TRUCK USING R404A REFRIGERANT
    Su, Zhiyong
    Zhao, Kunzheng
    Li, Haijun
    Zhang, Yibo
    THERMAL SCIENCE, 2024, 28 (3A): : 2033 - 2041
  • [10] SECOND LAW ANALYSIS OF AUTO CASCADE REFRIGERATION CYCLE USING MIXED HYDROCARBON REFRIGERANT R-600A/R-290/R170
    Hamad, Ahmed J.
    Khalifa, Abdul Hadi N.
    Salah, Hussein
    JURNAL TEKNOLOGI, 2018, 80 (06): : 9 - 17