Inverter-fed drives: Which motor stators are at risk?

被引:127
作者
Stone, G
Campbell, S
Tetreault, S
机构
关键词
D O I
10.1109/2943.863631
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
The surge voltage characteristics from a number of motors driven by inverter-fed drives (IFDs) were measured with both laboratory and purpose-built instrumentation. Premature failure of stator windings in low-voltage motors was found to be due to the partial discharges (PDs) created between turns. Measurements of all the surges revealed a wide range of surge-voltage magnitudes and rise times.
引用
收藏
页码:17 / 22
页数:6
相关论文
共 14 条
[11]   INVESTIGATION OF THE EFFECT OF REPETITIVE VOLTAGE SURGES ON EPOXY INSULATION [J].
STONE, GC ;
VANHEESWIJK, RG ;
BARTNIKAS, R .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 1992, 7 (04) :754-760
[12]   Estimation of voltage distribution on the inverter fed random wound induction motor windings supplied through feeder cable [J].
Toliyat, HA ;
Suresh, G ;
Abur, A .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 1999, 14 (04) :976-981
[13]  
WRIGHT MT, 1983, P IEE B JUL, P245
[14]  
Yin W, 1997, PROCEEDINGS: ELECTRICAL INSULATION CONFERENCE AND ELECTRICAL MANUFACTURING & COIL WINDING CONFERENCE, P379