Experimental and numerical study on the R744 ejector with a suction nozzle bypass

被引:16
作者
Bodys, Jakub [1 ]
Smolka, Jacek [1 ]
Palacz, Michal [1 ]
Haida, Michal [1 ]
Banasiak, Krzysztof [2 ]
Nowak, Andrzej J. [1 ]
机构
[1] Silesian Tech Univ, PL-44100 Gliwice, Poland
[2] Norwegian Univ Sci & Technol, N-7465 Trondheim, Norway
关键词
R744; ejector; Experimental tests; Performance improvement; Bypass; Numerical analysis; PERFORMANCE IMPROVEMENT; REFRIGERATION SYSTEMS; AUXILIARY ENTRAINMENT; COMPUTATIONAL MODEL; 2-PHASE EJECTOR; STEAM EJECTOR; HEAT-PUMP; EXPANSION; ENERGY; GEOMETRY;
D O I
10.1016/j.applthermaleng.2021.117015
中图分类号
O414.1 [热力学];
学科分类号
摘要
State-of-the-art R744 cooling cycles include highly efficient ejectors as a crucial element for competitive energy consumption in warm climates. However, an improvement is still possible, as shown in this study. This study is the first to experimentally investigate a construction of the R744 ejector with a modulated opening of the suction nozzle bypass duct. Four bypass positions along the ejector axis were tested using three sets of motive nozzle conditions characteristic of a refrigeration unit operating in a warm climate. Two levels of evaporation temperature, as well as the superheat influence, were investigated to evaluate the application potential. The efficiency of the prototype was equal to or greater than that of the standard construction because the closed bypass duct did not result in deteriorated ejector performance. The best bypass positioning resulted in improved efficiency for the pressure lift up to 7 bar. The maximum efficiency improvement was 37% with application potential for systems with low-pressure lift modes. The simulation of the full 3-D bypass ejector allowed for insight into the efficiency improvement. Finally, guidelines were given for further improvement considering the connection between the standard suction chamber and the bypass chamber.
引用
收藏
页数:13
相关论文
共 41 条
[1]   Development and performance mapping of a multi-ejector expansion work recovery pack for R744 vapour compression units [J].
Banasiak, Krzysztof ;
Hafner, Armin ;
Kriezi, Ekaterini E. ;
Madsen, Kenneth B. ;
Birkelund, Michael ;
Fredslund, Kristian ;
Olsson, Rickard .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2015, 57 :265-276
[2]   1D Computational model of a two-phase R744 ejector for expansion work recovery [J].
Banasiak, Krzysztof ;
Hafner, Armin .
INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2011, 50 (11) :2235-2247
[3]  
Bellos E., 2018, ENERG CONVERS MANAGE, VX
[4]   Ejectors on the cutting edge: The past, the present and the perspective [J].
Besagni, Giorgio .
ENERGY, 2019, 170 :998-1003
[5]   Ejector refrigeration: A comprehensive review [J].
Besagni, Giorgio ;
Mereu, Riccardo ;
Inzoli, Fabio .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2016, 53 :373-407
[6]   Performance improvement of the R744 two-phase ejector with an implemented suction nozzle bypass [J].
Bodys, Jakub ;
Smolka, Jacek ;
Banasiak, Krzysztof ;
Palacz, Michal ;
Haida, Michal ;
Nowak, Andrzej J. .
INTERNATIONAL JOURNAL OF REFRIGERATION, 2018, 90 :216-228
[7]   Progress and challenges in utilization of ejectors for cryogenic cooling [J].
Cao, H. S. ;
ter Brake, H. J. M. .
APPLIED THERMAL ENGINEERING, 2020, 167
[8]   Numerical assessment of ejector performance enhancement by means of two-bypass inlets [J].
Chen, Weixiong ;
Fan, Jiang ;
Huang, Chenxi ;
Liu, Shuangquan ;
Chong, Daotong ;
Yan, JunJie .
APPLIED THERMAL ENGINEERING, 2020, 171
[9]   Numerical assessment of ejector performance enhancement by means of combined adjustable-geometry and bypass methods [J].
Chen, Weixiong ;
Huang, Chenxi ;
Chong, Daotong ;
Yan, JunJie .
APPLIED THERMAL ENGINEERING, 2019, 149 :950-959
[10]   Impact of operational and geometrical factors on ejector performance with a bypass [J].
Chen, Weixiong ;
Chen, Huiqiang ;
Shi, Chaoyin ;
Xue, Kangkang ;
Chong, DaoTong ;
Yan, JunJie .
APPLIED THERMAL ENGINEERING, 2016, 99 :476-484