Distribution Line Parameter Estimation Under Consideration of Measurement Tolerances

被引:62
作者
Prostejovsky, Alexander M. [1 ]
Gehrke, Oliver [2 ]
Kosek, Anna M. [1 ]
Strasser, Thomas [3 ]
Bindner, Henrik W. [1 ]
机构
[1] Tech Univ Denmark, Dept Elect Engn, DK-4000 Roskilde, Denmark
[2] Tech Univ Denmark, Ctr Elect Power & Energy, DK-4000 Roskilde, Denmark
[3] AIT, Dept Energy, A-1210 Vienna, Austria
关键词
Grid topology; measurement uncertainty; monitoring; parameter estimation; parameter uncertainty; smart grids (SGs); state estimation (SE);
D O I
10.1109/TII.2016.2530620
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
State estimation and control approaches in electric distribution grids rely on precise electric models that may be inaccurate. This work presents a novel method of estimating distribution line parameters using only root mean square voltage and power measurements under consideration of measurement tolerances, noise, and asynchronous timestamps. A measurement tolerance compensation model and an alternative representation of the power flow equations without voltage phase angles are introduced. The line parameters are obtained using numeric methods. The simulation demonstrates in case of the series conductance that the absolute compensated error is -1.05% and -1.07% for both representations, as opposed to the expected uncompensated error of -79.68%. Identification of a laboratory distribution line using real measurement data grid yields a deviation of 6.75% and 4.00%, respectively, from a calculation based on the manufacturer's cable specifications and estimated line length. The transformed power flow equations deliver similar results despite the reduced problem complexity.
引用
收藏
页码:726 / 735
页数:10
相关论文
共 25 条
[1]  
Abur A., 2004, POWER SYSTEM STATE E
[2]   Uncertainty modelling in power system state estimation [J].
Al-Othman, AK ;
Irving, MR .
IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 2005, 152 (02) :233-239
[3]  
[Anonymous], 1994, Power System Analysis
[4]  
Bamberger Y., 2006, Vision and Strategy for Europe's Electricity Networks of the Future: European Technology PlatformSmartGrids
[5]   Transmission line conductor temperature impact on state estimation accuracy [J].
Bockarjova, Marija ;
Andersson, Goeran .
2007 IEEE LAUSANNE POWERTECH, VOLS 1-5, 2007, :701-706
[6]  
D'Antona G., 2012, 2012 IEEE International Workshop on Applied Measurements for Power Systems (AMPS) Proceedings, P1, DOI DOI 10.1109/AMPS.2012.6343999
[7]  
Dan A.M., 2011, 2011 IEEE Trondheim PowerTech, P1
[8]  
Dongli Jia, 2014, 2014 International Conference on Power System Technology (POWERCON 2014), P14, DOI 10.1109/POWERCON.2014.6993490
[9]   State Estimation for Smart Distribution Substations [J].
Gomez-Quiles, Catalina ;
Gomez-Exposito, Antonio ;
Jaen, Antonio de la Villa .
IEEE TRANSACTIONS ON SMART GRID, 2012, 3 (02) :986-995
[10]   Power Quality Early Warning Based on Anomaly Detection [J].
Gu, Wei ;
Bai, Jingjing ;
Yuan, Xiaodong ;
Zhang, Shuai ;
Wang, Yuankai .
JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY, 2014, 9 (04) :1171-1181