Analysis of voltage rise phenomena in electrical power network with high concentration of renewable distributed generations

被引:9
作者
Akinyemi, Ayodeji Stephen [1 ]
Musasa, Kabeya [1 ]
Davidson, Innocent E. [1 ]
机构
[1] Durban Univ Technol, Fac Engn & Built Environm, Dept Elect Power Engn, ZA-4000 Durban, South Africa
关键词
REACTIVE POWER; WIND TURBINES; FAULT RIDE; STRATEGY; STATCOM; SYSTEMS; DG;
D O I
10.1038/s41598-022-11765-w
中图分类号
O [数理科学和化学]; P [天文学、地球科学]; Q [生物科学]; N [自然科学总论];
学科分类号
07 ; 0710 ; 09 ;
摘要
The increasing penetration levels of renewable distributed generation (RDG) into a power system have proven to bring both positive and negative impacts. The occurrence of under voltage at the far end of a conventional electrical distribution network (DN) may not raise concern anymore with RDGs integration into a power system. However, a penetration of RDGs into power system may cause problems such as voltage rise or over-voltage and reverse power flows at the Point of Common Coupling (PCC) between RDG and DN. This research paper presents the impact of voltage rise effect and reverse power flow constraint in power system with high concentration of RDG. The analysis is conducted on a sample DN, i.e., IEEE 13-bus test system, with RDG penetration by considering the most critical scenario such as low power demand in DN and a peak power injection by RDG. For studying the impact of voltage rise and reverse power flow, a mathematical model of a DN integrating RDG is developed. Furthermore, a controller incorporating an advance control-algorithm is proposed to be installed at PCC between DN and RDG to regulate the voltage rise effects and to mitigate the reverse power flow when operating at a worst critical scenario of minimum load and maximum generation from RDG. The proposed control strategy also mitigates the voltage-current harmonic distortions, improves the power factor, and maintain the voltage stability at PCC. The simulations are carried out using MATLAB/Simulink software. Finally, recommendations are provided for the power producers to counteract the effects of voltage rise at PCC. The study has demonstrated that, voltage at PCC can be sustained with a high concentration of RDG during a worst-case scenario without a reverse power flow and voltage rise beyond grid code limits.
引用
收藏
页数:22
相关论文
共 60 条
[1]   Grid Integration Challenges of Wind Energy: A Review [J].
Ahmed, Shakir D. ;
Al-Ismail, Fahad S. M. ;
Shafiullah, Md ;
Al-Sulaiman, Fahad A. ;
El-Amin, Ibrahim M. .
IEEE ACCESS, 2020, 8 :10857-10878
[2]  
Akinyemi A. S., 2015, SO AFR U POW ENG C S
[3]  
Alinezhad MA., 2009, INT SCI INDEX, V3, P722
[4]  
[Anonymous], 2014, GRID CONN COD REN PO
[5]  
Arrik K., 2013, INT J SCI ENG RES, V4, P1293
[6]   A survey on control issues in renewable energy integration and microgrid [J].
Badal, Faisal R. ;
Das, Purnima ;
Sarker, Subrata K. ;
Das, Sajal K. .
PROTECTION AND CONTROL OF MODERN POWER SYSTEMS, 2019, 4 (01)
[7]   Voltage control with inverter-based distributed generation [J].
Bollen, MHJ ;
Sannino, A .
IEEE TRANSACTIONS ON POWER DELIVERY, 2005, 20 (01) :519-520
[8]  
Cañizares CA, 2000, 2000 IEEE POWER ENGINEERING SOCIETY WINTER MEETING - VOLS 1-4, CONFERENCE PROCEEDINGS, P1447, DOI 10.1109/PESW.2000.850192
[9]   Distributed reactive power generation control for voltage rise mitigation in distribution networks [J].
Carvalho, Pedro M. S. ;
Correia, Pedro F. ;
Ferreira, Luis A. F. M. .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2008, 23 (02) :766-772
[10]  
Dash R. L., 2021, INT C POW EL EN ICPE