Corrosive effects of the electromagnetic induction caused by the high voltage power lines on buried X70 steel pipelines

被引:22
作者
Ouadah, M. [1 ,2 ]
Touhami, O. [1 ]
Ibtiouen, R. [1 ]
Benlamnouar, M. F. [2 ]
Zergoug, M. [2 ]
机构
[1] Ecole Natl Polytech, Lab Rech Electrotech, 10 Ave Pasteur El Harrach,BP 182, Algiers 16200, Algeria
[2] CRTI, BP 64,Route Dely Ibrahim, Algiers 16033, Algeria
关键词
Electromagnetic induction; High voltage power line; Induced AC current density; X70 steel pipeline; Corrosion; Finite element method; DC-ELECTRIFIED RAILWAY; CATHODIC PROTECTION; STRAY CURRENT; ALTERNATING-CURRENT; GAS-PIPELINES; INTERFERENCE; MITIGATION; OVERHEAD; CRACKING; FIELDS;
D O I
10.1016/j.ijepes.2017.03.005
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper diagnoses the corrosive effects of the electromagnetic induction caused by double circuit high voltage power lines (HVPL) on the buried X70 steel pipelines. To achieve this objective, firstly the electromagnetic interference between the double circuit HVPL and the X70 steel pipeline (the distribution of the magnetic field and the induced AC current densities in the buried X70 steel pipeline) and the factors affecting this interference such as the vertical distance between the double circuit HVPL and the X70 steel pipeline, and the conductor phase sequence orientation were studied. Then, electrochemical measurements were used to characterize the corrosion polarization properties of X70 steel in simulated soil at various AC current densities. The results show that with an increase in the AC current density, the corrosion rate of the X70 steel increased, indicating that the induced AC current density has accelerated the corrosion degree of X70 steel, by comparison with that in the absence of the AC current density. We can conclude from these results that the electromagnetic induction caused by the double circuit high voltage power lines affects the electrochemical characteristic of the X70 steel pipeline and accelerates the corrosion of the pipeline. (C) 2017 Elsevier Ltd. All rights reserved.
引用
收藏
页码:34 / 41
页数:8
相关论文
共 37 条
[1]  
[Anonymous], 2001, AC CORR CATH PROT PI
[2]   Dynamic Stray Current Evaluations on Cut-and-Cover Sections of DC Metro Systems [J].
Charalambous, Charalambos A. ;
Aylott, Pete .
IEEE TRANSACTIONS ON VEHICULAR TECHNOLOGY, 2014, 63 (08) :3530-3538
[3]   Inductive interference on pipelines buried in multilayer soil due to magnetic fields from nearby faulted power lines [J].
Christoforidis, GC ;
Labridis, DP ;
Dokopoulos, PS .
IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, 2005, 47 (02) :254-262
[4]  
CIGRE Working Group 36.02, 1995, GUID INFL HIGH VOLT
[5]   Comparison of transient and power frequency-induced voltages on a pipeline parallel to an overhead transmission line [J].
Cotton, Ian ;
Kopsidas, Konstantinos ;
Zhang, Yang .
IEEE TRANSACTIONS ON POWER DELIVERY, 2007, 22 (03) :1706-1714
[7]   ANALYSIS OF ELECTRICAL INTERFERENCE FROM POWER-LINES TO GAS-PIPELINES .1. COMPUTATION METHODS [J].
DAWALIBI, FP ;
SOUTHEY, RD .
IEEE TRANSACTIONS ON POWER DELIVERY, 1989, 4 (03) :1840-1846
[8]   ANALYSIS OF ELECTRICAL INTERFERENCE FROM POWER-LINES TO GAS-PIPELINES .2. PARAMETRIC ANALYSIS [J].
DAWALIBI, FP ;
SOUTHEY, RD .
IEEE TRANSACTIONS ON POWER DELIVERY, 1990, 5 (01) :415-421
[9]   Stray Current Effects Mitigation in Subway Tunnels [J].
Dolara, Alberto ;
Foiadelli, Federica ;
Leva, Sonia .
IEEE TRANSACTIONS ON POWER DELIVERY, 2012, 27 (04) :2304-2311
[10]   Effect of alternating current on corrosion and effectiveness of cathodic protection of pipelines [J].
Fu, A. Q. ;
Cheng, Y. F. .