The application of condensate water as an additional cooling media intermittently in condenser of a split air conditioning

被引:9
|
作者
Ardita, I. N. [1 ]
Subagia, I. W. A. [1 ]
机构
[1] Bali State Polytech, Mech Engn Dept, Bali 80364, Indonesia
来源
2ND INTERNATIONAL JOINT CONFERENCE ON SCIENCE AND TECHNOLOGY (IJCST) 2017 | 2018年 / 953卷
关键词
D O I
10.1088/1742-6596/953/1/012059
中图分类号
O59 [应用物理学];
学科分类号
摘要
The condensate water produced by indoor a split air conditioning is usually not utilized and thrown away into the environment. The result of measurement shows that the temperature of condensate water produced by split air conditioning is quite low, that is 19-22 oC at the rate of 16-20 mL / min and it has PH balance. Under such conditions, Air Condensate produced by split air conditioning should still be recovered as an additional cooling medium on the condenser. This research will re-investigate the use of condensate water as an intermittent additional cooling of the condenser to increase the cooling capacity and performance of the air conditioning system. This research is done by experimental method whose implementation includes; designing and manufacturing of experimental equipment, mounting measuring tools, experimental data retrieval, data processing and yield analysis. The experimental results show that the use of condensate water as an intermittent additional cooling medium on split air conditioning condenser can increase the refrigeration effect about 2%, cooling capacity about 4% and 7% of COP system. Experimental results also show a decrease in power consumption in the system compressor about 3%
引用
收藏
页数:7
相关论文
共 50 条
  • [1] Characteristics of air conditioning system with an additional condenser
    Goto, Makoto
    Tanifuji, Koji
    Fujita, Masahiro
    Yamauchi, Tomohiro
    Ohuchida, Satoshi
    Nagata, Kenji
    Ueno, Isao
    Hasegawa, Tatsuya
    PROCEEDINGS OF THE 3RD ASIAN CONFERENCE ON REFRIGERATION AND AIR-CONDITIONING VOLS I AND II, 2006, : 23 - +
  • [2] Experimental Study for the Effect of Pre-Cooling the Condenser Inlet Air of Split Type Air Conditioning Unit
    Faisal, Safaa H.
    Hammadi, Salman H.
    Mutlag, Saif S.
    ENGINEERING JOURNAL-THAILAND, 2018, 22 (05): : 67 - 85
  • [3] Experimental study on the effect of condensate water on the performance of split air conditioning system
    Yang, Hua
    Pei, Na
    Liu, Liansheng
    Fan, Man
    Qin, Yue
    ENERGY REPORTS, 2021, 7 : 840 - 851
  • [4] Experimental study of split air conditioner with and without trombone coil condenser as air conditioning water heater
    Aziz, Azridjal
    Satria, Arya Bhima
    Mainil, Rahmat Iman
    INTERNATIONAL JOURNAL OF AUTOMOTIVE AND MECHANICAL ENGINEERING, 2015, 12 : 3043 - 3057
  • [5] The Feasibility on the Case that the Air Conditioning Condensate Water is used as the Make-up Water of Cooling Tower
    Liu, Nailing
    Li, Zhe
    10TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATION AND AIR CONDITIONING, ISHVAC2017, 2017, 205 : 3557 - 3562
  • [7] Experimental study on the influence of the water spray cooling on air-cooled condenser of the split-type air conditioner
    Charoensin-O-larn, Roytor
    Kavee, Narin
    Klinbun, Jirapol
    CASE STUDIES IN THERMAL ENGINEERING, 2024, 61
  • [8] Experimental investigation of air conditioning system using evaporative cooling condenser
    Wang, Tianwei
    Sheng, Chenguang
    Nnanna, A. G. Agwu
    ENERGY AND BUILDINGS, 2014, 81 : 435 - 443
  • [9] Experimental investigation of air conditioning system using evaporative cooling condenser
    Wang, T. (tianwei0512@gmail.com), 1600, Elsevier Ltd (81):
  • [10] Process Analysis and Application of Spray Cooling for Indirect Air Cooling Condenser
    Sun, Zhen
    Liu, Feng
    Zhang, Zhenzhou
    Han, Naibo
    2016 3RD INTERNATIONAL CONFERENCE ON MECHANICAL, INDUSTRIAL, AND MANUFACTURING ENGINEERING (MIME 2016), 2016, : 72 - 76