Performance evaluation and modeling of a hybrid cooling system combining a screw water chiller with a ground source heat pump in a building

被引:48
作者
Jeon, Jongug [1 ]
Lee, Sunil [1 ]
Hong, Daehie [1 ]
Kim, Yongchan [1 ]
机构
[1] Korea Univ, Dept Mech Engn, Seoul 136713, South Korea
关键词
Ground source heat pump (GSHP); Screw water chiller; HVAC system; Modeling; AIR-CONDITIONING SYSTEM; SIMULATION; VALIDATION; FLOW;
D O I
10.1016/j.energy.2010.01.016
中图分类号
O414.1 [热力学];
学科分类号
摘要
The performance of a hybrid cooling system that combines a screw water chiller with a ground source heat pump (GSHP) was measured and analyzed at various cooling loads. In addition, the hybrid cooling system in a building was modelled sophisticatedly using EnergyPlus and then validated with the measured data. The coefficient of performance of the GSHP was lower than that of a conventional chiller in the monitored building, but the hybrid cooling system helped to stably provide the required cooling capacity at high-load conditions. The mean bias error and the normalized root-mean squared error of the predicted cooling load of the building were -8% and 12.4%, respectively. The hybrid cooling system was simulated by varying four operating parameters: the operating schedule, chilled water temperature (T-cw), dry-bulb temperature (T-DB), and entering water temperature (T-EW). The Tcw is ascertained as being the most effective control parameter in the hybrid cooling system. (C) 2010 Elsevier Ltd. All rights reserved.
引用
收藏
页码:2006 / 2012
页数:7
相关论文
共 21 条
[1]  
*ASHRAE, 1986, 2 ASHRAE
[2]   Thermodynamic analysis of a ground-source heat pump system for district heating [J].
Hepbasli, A .
INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2005, 29 (07) :671-687
[3]  
Jin H., 2002, THESIS OKLAHOMA STAT
[4]  
Jin H., 2002, ASHRAE Transactions, V108, P3
[5]  
Murugappan A., 2002, THESIS OKLAHOMA STAT
[6]   Optimal planning and economic evaluation of cogeneration system [J].
Oh, Si-Doek ;
Lee, Ho-Jun ;
Jung, Jung-Yeul ;
Kwak, Ho-Young .
ENERGY, 2007, 32 (05) :760-771
[7]   Modeling and performance evaluation of ground source (geothermal) heat pump systems [J].
Ozgener, Onder ;
Hepbasli, Arif .
ENERGY AND BUILDINGS, 2007, 39 (01) :66-75
[8]   Performance validation and energy analysis of HVAC systems using simulation [J].
Salsbury, T ;
Diamond, R .
ENERGY AND BUILDINGS, 2000, 32 (01) :5-17
[9]  
Sankaranarayanan K.P., 2005, THESIS OKLAHOMA STAT
[10]  
Song Doosam, 2007, International Journal of Air-Conditioning and Refrigeration, V15, P137