Evaluation of service aged 35 kV TR-XLPE URD cables

被引:12
作者
Katz, C [1 ]
Walker, M
机构
[1] Cable Technol Labs Inc, New Brunswick, NJ USA
[2] Houston Lighting & Power Co, Houston, TX USA
关键词
D O I
10.1109/61.660836
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper provides information on aging of URD cable insulated with tree-retardant crosslinked polyethylene (TR-XLPE) compound, installed in a typical utility environment, Numerous evaluations were performed on samples of the cables aged up to 7 years in-service, AC and impulse voltage breakdown data are compared with data for similar 35 kV ethylene propylene rubber (EPR) and crosslinked polyethylene (XLPE) insulated cables removed from the same utility system, The data show that, to date, the rate of degradation of TR-XLPE cables is less than that of the EPR and XLPE insulated cables, Extrapolation of the data, assuming the same rate,indicates TR-XLPE cable will have the longest life.
引用
收藏
页码:1 / 6
页数:6
相关论文
共 9 条
[1]  
*ASS ED ILL CO, 1987, SPEC THERM CROSSL PO
[2]  
EICHHORN RM, 1991, JICABLE 91, P145
[3]   EFFECTS OF VOLTAGE SURGES ON EXTRUDED DIELECTRIC CABLE LIFE - PROJECT UPDATE [J].
HARTLEIN, RA ;
HARPER, VS ;
NG, H .
IEEE TRANSACTIONS ON POWER DELIVERY, 1994, 9 (02) :611-619
[4]   COMPARATIVE-EVALUATION BY LABORATORY AGING OF 15 KV AND 35-KV EXTRUDED DIELECTRIC CABLES [J].
KATZ, C ;
WALKER, M ;
DYNDUL, J .
IEEE TRANSACTIONS ON POWER DELIVERY, 1990, 5 (02) :816-824
[5]   AN ASSESSMENT OF FIELD-AGED 15KV AND 35KV ETHYLENE-PROPYLENE RUBBER INSULATED CABLES [J].
KATZ, C ;
WALKER, M ;
LANDINGER, CC ;
SILVER, DA .
IEEE TRANSACTIONS ON POWER DELIVERY, 1995, 10 (01) :25-33
[6]  
KATZ C, 1984, JICABLE 84, P127
[7]  
KATZ C, 1994, P 43 INS WIR CABL S, P450
[8]  
MATEY G, 1991, JICABLE 91, P154
[9]  
NAYBOUR RD, 1991, JICABLE 91, P167