High Performance Data Centers and Energy Efficiency Potential in Greece

被引:14
作者
Balaras, Constantinos A. [1 ]
Lelekis, John [2 ]
Dascalaki, Elena G. [1 ]
Atsidaftis, Dimitris [3 ]
机构
[1] Natl Observ Athens, Inst Environm Res & Sustainable Dev, GR-15236 Palea Penteli, Greece
[2] Marathonomahon 10A, GR-15124 Athens, Greece
[3] DIAMAR SA, 22 Keas Str, GR-15127 Melissia, Greece
来源
SUSTAINABLE SYNERGIES FROM BUILDINGS TO THE URBAN SCALE | 2017年 / 38卷
关键词
data centers; high performance; ASHRAE datacom series; energy audit; power usage effectiveness; PUE;
D O I
10.1016/j.proenv.2017.03.091
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Data centers are amongst the most complex and energy demanding building environments. The trends of increasing data center capacity and power use by information technology equipment, re-emphasize the need to reduce cooling loads, first cost for HVAC equipment, and finally related energy and operational costs. The first part of the paper presents an overview of relevant information and available resources for the efficient design and operation of these critical environments. The second part considers two large data centers located in Athens that serve two major Hellenic banks as case studies in order to investigate and quantify the potential measures for improving their energy performance. The two facilities were audited and actual energy consumption were used for an energy assessment. According to simulation results of various efficiency measures, the Power Usage Effectiveness may be improved from 2.49 to 2.11 for the first case study and from 1.89 to 1.66 for the second one. (C) 2017 The Authors. Published by Elsevier B.V.
引用
收藏
页码:107 / 114
页数:8
相关论文
共 18 条
[1]  
[Anonymous], DAT SER
[2]  
[Anonymous], HDB HVAC APPL
[3]  
Aravanis AI, 2015, IEEE GLOBE WORK
[4]  
BEATY DL, 2014, ASHRAE J, V56, P74
[5]  
Beaty DL, 2015, ASHRAE J, V57, P76
[6]  
Bruschi J, 2011, DOEGO1020102956 NAT
[7]   Improving energy efficiency of dedicated cooling system and its contribution towards meeting an energy-optimized data center [J].
Cho, Jinkyun ;
Kim, Yundeok .
APPLIED ENERGY, 2016, 165 :967-982
[8]  
CIBSE, 2012, DAT CTR INTR CONC DE
[9]  
LBNL, HIGH PERF BUILD HIGH
[10]   Communication-Awareness for Energy-Efficiency in Datacenters [J].
Nabavinejad, Seyed Morteza ;
Goudarzi, Maziar .
ADVANCES IN COMPUTERS, VOL 100: ENERGY EFFICIENCY IN DATA CENTERS AND CLOUDS, 2016, 100 :201-254