Distributed Voltage Control with Electric Springs: Comparison with STATCOM

被引:99
作者
Luo, Xiao [1 ]
Akhtar, Zohaib [2 ]
Lee, Chi Kwan [1 ]
Chaudhuri, Balarko [2 ]
Tan, Siew-Chong [1 ]
Hui, Shu Yuen Ron [1 ,3 ]
机构
[1] Univ Hong Kong, Dept Elect & Elect Engn, Hong Kong, Hong Kong, Peoples R China
[2] Univ London Imperial Coll Sci Technol & Med, Dept Elect & Elect Engn, London SW7 2AZ, England
[3] Univ London Imperial Coll Sci Technol & Med, London SW7 2AZ, England
基金
英国工程与自然科学研究理事会;
关键词
Demand response; electric springs (ES); STATic COMpensator (STATCOM); voltage control; voltage regulation;
D O I
10.1109/TSG.2014.2345072
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The concept of electric spring (ES) has been proposed recently as an effective means of distributed voltage control. The idea is to regulate the voltage across the critical (C) loads while allowing the noncritical (NC) impedance-type loads (e.g., water heaters) to vary their power consumption and thus contribute to demand-side response. In this paper, a comparison is made between distributed voltage control using ES against the traditional single point control with STATic COMpensator (STATCOM). For a given range of supply voltage variation, the total reactive capacity required for each option to produce the desired voltage regulation at the point of connection is compared. A simple case study with a single ES and STATCOM is presented first to show that the ES and STATCOM require comparable reactive power to achieve similar voltage regulation. Comparison between a STATCOM and ES is further substantiated through similar case studies on the IEEE 13-bus test feeder system and also on a part of the distribution network in Sha Lo Wan Bay, Hong Kong. In both cases, it turns out that a group of ESs achieves better total voltage regulation than STATCOM with less overall reactive power capacity. Dependence of the ES capability on proportion of critical and NC load is also shown.
引用
收藏
页码:209 / 219
页数:11
相关论文
共 16 条
[1]  
[Anonymous], 2013, HONG KONG EN END US
[2]  
[Anonymous], 2006, IEEE 13 NODE TEST FE
[3]   Demand Dispatch [J].
Brooks, Alec ;
Lu, Ed ;
Reicher, Dan ;
Spirakis, Charles ;
Weihl, Bill .
IEEE POWER & ENERGY MAGAZINE, 2010, 8 (03) :20-29
[4]  
Chaudhuri N. R., IEEE T SMAR IN PRESS
[5]   Reactive power compensation technologies:: State-of-the-art review [J].
Dixon, J ;
Morán, L ;
Rodríguez, J ;
Domke, R .
PROCEEDINGS OF THE IEEE, 2005, 93 (12) :2144-2164
[6]  
Hingorani NG., 2000, Understanding FACTS: Concepts and Technology of Flexible AC Transmission Systems
[7]  
Lee C. K., 2013, IEEE T SMART GRID, V4, P1
[8]   Hardware and Control Implementation of Electric Springs for Stabilizing Future Smart Grid With Intermittent Renewable Energy Sources [J].
Lee, Chi Kwan ;
Chaudhuri, Balarko ;
Hui, Shu Yuen .
IEEE JOURNAL OF EMERGING AND SELECTED TOPICS IN POWER ELECTRONICS, 2013, 1 (01) :18-27
[9]   Droop Control of Distributed Electric Springs for Stabilizing Future Power Grid [J].
Lee, Chi Kwan ;
Chaudhuri, N. Ray ;
Chaudhuri, Balako ;
Hui, S. Y. R. .
IEEE TRANSACTIONS ON SMART GRID, 2013, 4 (03) :1558-1566
[10]  
Miller T. J. E., 1982, Reactive power control in electric systems