Effect of Arcing Time on Voltage Distribution of Double-Break Vacuum Circuit Breaker During the Transient Recovery Voltage Rising Phase

被引:11
作者
Zhang, Hao [1 ]
Liao, Minfu [1 ]
Fu, Yifan [1 ]
Chen, Zhanqing [1 ]
Dong, Huaqing [1 ]
Zou, Jiyan [1 ]
机构
[1] Dalian Univ Technol, Sch Elect Engn, Dalian 116024, Peoples R China
基金
中国国家自然科学基金;
关键词
Capacitors; Circuit breakers; Transient analysis; Vacuum arcs; TV; Capacitance; Switches; Arcing time; double-break vacuum circuit breaker; transient recovery voltage (TRV) rising phase; voltage distribution; GRADING CAPACITORS;
D O I
10.1109/TPS.2021.3065739
中图分类号
O35 [流体力学]; O53 [等离子体物理学];
学科分类号
070204 ; 080103 ; 080704 ;
摘要
Grading capacitors are required to balance the voltage distribution of the double-break vacuum circuit breaker. However, large grading capacitors increase the magnitude and duration of the reignition current. To reduce grading capacitors, a synthetic circuit with double vacuum breaks was set up to study the effects of arcing time on voltage distribution. The voltage distribution of the upper break decreases from 61% to 52% with arcing times of two breaks decreasing from 6.6 to 3.4 ms synchronously. The experimental results demonstrate that reducing the arcing times can balance the voltage distribution during the transient recovery voltage (TRV) rising phase. The unbalance of TRV distribution can be further improved by adopting appropriate arcing times in the two breaks with grading capacitors having a capacitance of 3000 pF.