An Experimental Study on the Energy and Exergy Performance of an Air-Type PVT Collector with Perforated Baffle

被引:20
作者
Kim, Jin-Hee [1 ]
Yu, Ji-Suk [2 ]
Kim, Jun-Tae [3 ]
机构
[1] Kongju Natl Univ, Green Energy Technol Res Ctr, Cheonan 31080, South Korea
[2] Kongju Natl Univ, Zero Energy Bldg Lab, Grad Sch Energy Syst Engn, Cheonan 31080, South Korea
[3] Kongju Natl Univ, Dept Architectural Engn, Cheonan 31080, South Korea
基金
新加坡国家研究基金会;
关键词
air-type PVT collector; ISO; 9806; standard; outdoor testing; energy analysis; exergy analysis; SYSTEM; IMPROVEMENT; NANOFLUIDS; PV/T;
D O I
10.3390/en14102919
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
BIPV (Building Integrated Photovoltaic) system is a building envelope technology that generates energy by converting solar energy into electricity. However, after producing electrical energy, the remaining solar energy is transferred as heat, raising the temperature at the rear of the BIPV module, and reducing electrical efficiency. On the other hand, a PVT (Photovoltaic Thermal) collector is a device that generates electricity from a PV module and at the same time uses the heat transferred to the air layer inside the collector. In general, the performance of air-type PVT collectors is based on energy analysis using the first law of thermodynamics. Since this performance does not take into account the loss amount, it is not the actual amount of power generation and preheat of the collector that can be used. Therefore, an exergy analysis based on the second law of thermodynamics considering the amount of energy loss must be performed. In this paper, an air-type PVT collector to which perforated baffles were applied was tested through outdoor experiments based on ISO 9806 standard. The total energy (thermal and electrical characteristics) and exergy according to the flow rate (100, 150, and 200 m(3)/h), solar radiation, and rear temperature of the PV module of the air-type PVT collector were analyzed. As a result, the total exergy efficiency of the air-type PVT collector with perforated baffles was 24.8-30.5% when the total energy efficiency was 44.1-63.3%.
引用
收藏
页数:13
相关论文
共 50 条
  • [41] Performance evaluation of water and air based PVT solar collector for hydrogen production application
    Senthilraja, S.
    Gangadeui, R.
    Marimuthu, R.
    Baskaran, M.
    INTERNATIONAL JOURNAL OF HYDROGEN ENERGY, 2020, 45 (13) : 7498 - 7507
  • [42] Experimental Study and Exergy Analysis About the Flat Plate Solar Collector
    Kareem, Fadhil Abdulrazzaq
    Skheal, Osamah Raad
    Lafta, Noor Samir
    INTERNATIONAL JOURNAL OF INTEGRATED ENGINEERING, 2022, 14 (06): : 156 - 171
  • [43] Energy and exergy analysis of a glazed solar preheating collector wall with non-uniform perforated corrugated plate
    Gao, Meng
    Fan, Jianhua
    Furbo, Simon
    Xiang, Yutong
    RENEWABLE ENERGY, 2022, 196 : 1048 - 1063
  • [44] Energy, Exergy and Efficiency Analysis of a Flat Plate Solar Collector Used as Air Heater
    Hanif, Muhammad
    Khattak, Mansoor Khan
    Khan, Maazullah
    Ramzan, Muhammad
    Abdurab
    SAINS MALAYSIANA, 2018, 47 (05): : 1061 - 1067
  • [45] Experimental investigation of energy and exergy performance of square and circular solar ponds
    Dehghan, Ali A.
    Movahedi, Alireza
    Mazidi, Mohsen
    SOLAR ENERGY, 2013, 97 : 273 - 284
  • [46] Energy and exergy assessment of a flat plate solar thermal collector by examine silicon carbide nanofluid: An experimental study for sustainable energy
    Ajeena, Ahmed M.
    Farkas, Istvan
    Vig, Piroska
    APPLIED THERMAL ENGINEERING, 2024, 236
  • [47] Performance Evaluation of PVT Air Collector Coupled with a Triangular Block in Actual Climate Conditions in Korea
    Choi, Hwi-Ung
    Choi, Kwang-Hwan
    ENERGIES, 2022, 15 (11)
  • [48] Experimental study of using nano-(GNP, MWCNT, and SWCNT)/water to investigate the performance of a PVT moduleEnergy and exergy analysis
    Ammar Alwan Sywan Alshaheen
    Ali Kianifar
    Asghar Baradaran Rahimi
    Journal of Thermal Analysis and Calorimetry, 2020, 139 : 3549 - 3561
  • [49] Experimental and numerical study of the effect of integrating plus-shaped perforated baffles to solar air collector in drying application
    Khanlari, Ataollah
    Guler, Hande Ozge
    Tuncer, Azim Dogus
    Sirin, Ceylin
    Bilge, Yasar Can
    Yilmaz, Yusuf
    Gungor, Afsin
    RENEWABLE ENERGY, 2020, 145 : 1677 - 1692
  • [50] Performance study of a novel solar air collector
    Peng, Donggen
    Zhang, Xiaosong
    Dong, Hua
    Lv, Kun
    APPLIED THERMAL ENGINEERING, 2010, 30 (16) : 2594 - 2601