Vapour condensation of R22 retrofit substitutes R417A, R422A and R422D on CuNi turbo C tubes

被引:32
作者
Fernandez-Seara, Jose [1 ]
Uhia, Francisco J. [1 ]
Diz, Ruben [1 ]
Alberto Dopazo, J. [1 ]
机构
[1] Univ Vigo, ETS Ingenieros Ind, Area Maquinas & Motores Term, Vigo 36310, Spain
来源
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID | 2010年 / 33卷 / 01期
关键词
Heat exchanger; Condenser; Condensation; Shell; Experiment; Heat transfer; R22; R417A; R422A; R422D; HEAT-TRANSFER COEFFICIENTS; HORIZONTAL SMOOTH TUBE; INTEGRAL-FIN TUBES; 3 HFC REFRIGERANTS; ZEOTROPIC MIXTURES; STAGGERED BUNDLE; BINARY-MIXTURE; REPLACING R22; PURE FLUID; PART I;
D O I
10.1016/j.ijrefrig.2009.09.006
中图分类号
O414.1 [热力学];
学科分类号
摘要
Heat transfer coefficients (HTCs) for outer condensation of R22 and vapours of its retrofit substitutes R417A, R422A and R422D on 90/10 CuNi Turbo C tubes were experimentally measured. The tubes have 19.05 mm nominal outside diameter, 40 fins per inch (1575 fpm) on the outer surface and a smooth inner surface. The effective condensing length per tube was 1895 mm. Experimental data are reported at vapour saturation temperature of 40 degrees C and wall subcoolings from around 1.5 to 8 degrees C. A rapid increase of the HTCs for low wall subcoolings attributable to the presence of the hydrocarbon in the mixtures was found. For wall subcoolings greater than around 3 degrees C, the condensation HTCs slightly increase with raising the wall subcooling and they are for vapours of R417A, R422A and R422D lower by 65-76%, 24-31% and 60-67% than the HTCs for R22, respectively. Comparisons of the condensation performance amongst the different refrigerants and experimental enhancement factors for the condensation of R22 on 90/10 CuNi Turbo C tubes are reported in the paper. (c) 2009 Elsevier Ltd and IIR. All rights reserved.
引用
收藏
页码:148 / 157
页数:10
相关论文
共 29 条
[1]  
[Anonymous], 1995, Guide to the Expression of Uncertainty in Measurement, Corrected and reprinted 1995, P9
[2]  
[Anonymous], NIST REFERENCE FLUID
[3]   Comparison of R407C and R417A heat transfer coefficients and pressure drops during flow boiling in a horizontal smooth tube [J].
Aprea, C. ;
Greco, A. ;
Rosato, A. .
ENERGY CONVERSION AND MANAGEMENT, 2008, 49 (06) :1629-1636
[4]   Experimental comparison of R22 with R417A performance in a vapour compression refrigeration plant subjected to a cold store [J].
Aprea, C ;
Renno, C .
ENERGY CONVERSION AND MANAGEMENT, 2004, 45 (11-12) :1807-1819
[5]   Experimental study and modelling of heat transfer during condensation of pure fluid and binary mixture on a bundle of horizontal finned tubes [J].
Belghazi, M ;
Bontemps, A ;
Marvillet, C .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2003, 26 (02) :214-223
[6]   Condensation heat transfer on enhanced surface tubes: Experimental results and predictive theory [J].
Belghazi, M ;
Bontemps, A ;
Marvillet, C .
JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 2002, 124 (04) :754-761
[7]   Condensation heat transfer of a pure fluid and binary mixture outside a bundle of smooth horizontal tubes. Comparison of experimental results and a classical model [J].
Belghazi, M ;
Bontemps, A ;
Signe, JC ;
Marvillet, C .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2001, 24 (08) :841-855
[8]   Two-phase heat transfer coefficients of three HFC refrigerants inside a horizontal smooth tube, part II: condensation [J].
Boissieux, X ;
Heikal, MR ;
Johns, RA .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2000, 23 (05) :345-352
[9]   Two-phase heat transfer coefficients of three HFC refrigerants inside a horizontal smooth tube, part I: evaporation [J].
Boissieux, X ;
Heikal, MR ;
Johns, RA .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2000, 23 (04) :269-283
[10]  
CHENG WY, 1996, INT COMMUN HEAT MASS, V23, P9