Lightning Incidence of Wind Farm Underground Power Cable Networks

被引:0
|
作者
Sarajcev, Petar [1 ]
Goic, Ranko [1 ]
机构
[1] Univ Split, Fac Elect Engn Mech Engn & Naval Architecture, Dept Power Syst, HR-21000 Rudera Boskovica Bb, Split, Croatia
来源
INTERNATIONAL REVIEW OF ELECTRICAL ENGINEERING-IREE | 2010年 / 5卷 / 03期
关键词
Lightning; Log-normal Distribution; Underground Cables; Wind Farm; TRANSMISSION-LINES; BURIED CABLES; DISTRIBUTIONS; DISTURBANCES; TRANSIENTS; PROTECTION; PARAMETERS; STROKES;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents a general procedure for the estimation of the lightning incidence of underground power cable networks, in this particular case, associated with modern wind farms. The modern wind farms are often comprised of several dozens of wind turbines mutually interconnected through an extended medium voltage underground power cable network It is unfortunate coincidence that these wind farms are often located in regions of increased lightning activity, which stems from the fact that regions with high wind potential often coincide with regions of increased thunderstorm activity. Furthermore, wind farm locations could additionally be accompanied with the high soil resistivity of the terrain, which would provide favorable conditions for the lightning-initiated damage of the associated wind farm cable networks. Hence, it is considered prudent to estimate the lightning incidence of the wind farm underground power cable networks and, if necessary, provide additional cable-damage mitigation techniques combined with the appropriate overvoltage protection measures. Copyright (C) 2010 Praise Worthy Prize S.r.l. - All rights reserved.
引用
收藏
页码:1244 / 1254
页数:11
相关论文
共 50 条
  • [1] The Technology of Submarine Power Cable for Offshore Wind Farm
    Journal of the Institute of Electrical Engineers of Japan, 2021, 141 (11): : 686 - 689
  • [2] Lightning transient characteristics of cable power collection system in wind power plants
    Li, Xianqiang
    Wang, Jianguo
    Wang, Yu
    Fan, Yadong
    Zhang, Baoquan
    Wang, Shunchao
    Zhou, Mi
    Cai, Li
    IET Renewable Power Generation, 2015, 9 (08) : 1025 - 1032
  • [3] Lightning Fault Rate of Power Distribution Line in Wind Farm in Winter Lightning Area
    Michishita, Koji
    Yokoyama, Shigeru
    PROCEEDINGS OF THE 21ST INTERNATIONAL SYMPOSIUM ON HIGH VOLTAGE ENGINEERING, VOL 1, 2020, 598 : 1377 - 1389
  • [4] Induced Electromagnetic Fields on Underground Cable Due to Lightning-Struck Wind Tower
    Rizk, Mohammad E. M.
    Ghanem, Abdelhady
    Abulanwar, Sayed
    Shahin, Ahmed
    Baba, Yoshihiro
    Mahmood, Farhan
    Ismael, Islam
    IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, 2023, 65 (06) : 1684 - 1694
  • [5] Optimisation of power cable ampacity in offshore wind farm applications
    Hoyer-Hansen, M.
    Helleso, S. M.
    Solheim, K. T.
    Mehammer, E. B.
    Eberg, E.
    Pedersen, P. A.
    EERA DEEPWIND OFFSHORE WIND R&D CONFERENCE, DEEPWIND 2022, 2022, 2362
  • [6] Optimizing wind farm cable routing considering power losses
    Fischetti, Martina
    Pisinger, David
    EUROPEAN JOURNAL OF OPERATIONAL RESEARCH, 2018, 270 (03) : 917 - 930
  • [7] Protection of Lightning Disturbances on MV Underground Cable
    Omidiora, Michael A.
    Lehtonen, Matti
    INTERNATIONAL REVIEW OF ELECTRICAL ENGINEERING-IREE, 2010, 5 (01): : 317 - 326
  • [8] Reserve Power Arrangements in Rural Area Underground Cable Networks
    Haakana, Juha
    Kaipia, Tero
    Lassila, Jukka
    Partanen, Jarmo
    IEEE TRANSACTIONS ON POWER DELIVERY, 2014, 29 (02) : 589 - 597
  • [9] Lightning overvoltage analysis in wind farm
    Vahidi, B.
    Mousavi, O. Alizadeh
    Hosseinian, S. H.
    TENCON 2007 - 2007 IEEE REGION 10 CONFERENCE, VOLS 1-3, 2007, : 1067 - 1069
  • [10] On the Lightning Incidence to Wind Farms
    Long, Mengni
    Becerra, Marley
    Thottappillil, Rajeev
    2016 33RD INTERNATIONAL CONFERENCE ON LIGHTNING PROTECTION (ICLP), 2016,