PHASOR-BASED TRANSIENT EARTH-FAULT PROTECTION

被引:0
作者
Gajic, Zoran [1 ]
Zubic, Sinisa [1 ]
Kockott, Mike [2 ]
机构
[1] Hitachi ABB Power Grids Sweden AB, Grid Automat Prod, Vasteras, Sweden
[2] Hitachi ABB Power Grids, 901 Main Campus Dr, Raleigh, NC 27606 USA
来源
2021 74TH CONFERENCE FOR PROTECTIVE RELAY ENGINEERS (CPRE) | 2021年
关键词
Transient ground-fault protection; High-impedance grounding; Resonant grounding; Earth-fault;
D O I
10.1109/CPRE48231.2021.9429719
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The main problem for any transient earth-fault (i.e. ground-fault) protection in high-impedance grounded system is to extract the useful signal components from the measured residual current I-0. Many used solutions are based on either complete fundamental frequency and/or complete higher harmonic phasors. However, for the fundamental frequency current phasor of the I-0 current, only the I-01*cos(phi(1)) component has useful physical meaning during the ground fault transient, while the I-01*sin(phi(1)) component is just a disturbing part which can only cause the wrong operation of the protection. At the same time, for all higher harmonic phasors of the I-0 current the situation is exactly the opposite. The I-0h*sin(phi(h)) is the useful component with a clear physical meaning while the I-0h*cos(phi(h)) component is a disturbing part which can only upset the ground-fault measurement. In the proposed solution, only the two useful phasor components are used. They are first integrated over short period of time deriving values proportional to the energy content of the two original signals. Only the positive or negative sign of these integrated values is then used in the design to determine the direction of the ground fault. Before being used for directionality check, the integrated value must also exceed the pre-set minimum threshold level, for security reasons. Another important property of these two quantities is that they will be approximately equal to zero during all operating conditions of the protected network except during the transient period of the ground-fault and consequently they can be then easily detected.
引用
收藏
页数:26
相关论文
共 17 条
[1]  
Altonen J., 2017, CIRED 24 INT C EL DI CIRED 24 INT C EL DI
[2]  
[Anonymous], 1988, UG033110E ABB REL UG033110E ABB REL
[3]  
[Anonymous], 1991, 1MDA07SV ABB REL 1MDA07SV ABB REL
[4]  
[Anonymous], 1987, B033014 ABB REL B033014 ABB REL
[5]  
[Anonymous], 1964, EL TRANSM DISTR REF EL TRANSM DISTR REF, P643
[6]  
[Anonymous], 2020, 1MRK506370UEN ABB 1MRK506370UEN ABB
[7]  
[Anonymous], 2018, AN200EN003 VAMP AN200EN003 VAMP
[8]  
Colding S., CIGRE SESS PAR FRANC CIGRE SESS PAR FRANC
[9]  
Gajic Z, 2020, IET DEV POW SYST PRO IET DEV POW SYST PRO
[10]  
Guldbrand A., 2009, THESIS LUND U THESIS LUND U