Performance comparison between bypass cycle and injection cycle for sub-cooling methods in multi-split variable refrigerant flow (VRF) system in hot seasons

被引:10
作者
Min, Byungchae [1 ]
Jang, Seokhoon [1 ]
Lee, Taemin [2 ]
Bae, Heunghee [1 ]
Moon, Cheoreon [1 ]
Choi, Gyungmin [2 ]
机构
[1] H&A Solut Co, LG Elect, SAC Res Engn Div, 84 Wanam Ro, Changwon Si 51554, Gyeongsangnam D, South Korea
[2] Pusan Natl Univ, Sch Mech Engn, Busan 46283, South Korea
来源
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID | 2019年 / 107卷
关键词
Variable refrigerant flow system; Sub-cooling method; Bypass cycle; Injection cycle; Numerical simulation; HEAT-PUMP SYSTEM; VAPOR INJECTION; SIMULATION; EQUATIONS; R410A; MODEL;
D O I
10.1016/j.ijrefrig.2019.07.010
中图分类号
O414.1 [热力学];
学科分类号
摘要
In this study, the performance of a multi-split VRF system using the bypass cycle and injection cycle is evaluated using the numerical simulation as a possible sub-cooling method to prevent flash gas generation in liquid pipelines. The simulation for the multi-split VRF system is developed by considering the applications of the bypass cycle and injection cycle, and is validated with experimental data. The bypass cycle and injection cycle in the multi-split VRF system yield improvements in their cooling capacities of the order of 3.22% and 13.43%, respectively, and energy efficient ratio (EER) of the order of 1.98% and 1.72%, respectively. The input power of the injection cycle is reduced by up to 4.45% when the performance of the multi-split VRF systems with bypass cycle and injection cycle is compared under the same cooling capacity conditions. (C) 2019 Published by Elsevier Ltd.
引用
收藏
页码:202 / 213
页数:12
相关论文
共 22 条
[1]  
Afify R, 2008, ASHRAE J, V50, P52
[2]  
[Anonymous], 2005, 372005 ANSIASHRAE
[3]   Performance comparison between R410A and R32 multi-heat pumps with a sub-cooler vapor injection in the heating and cooling modes [J].
Cho, Ii Yong ;
Seo, HyeongJoon ;
Kim, Dongwoo ;
Kim, Yongchan .
ENERGY, 2016, 112 :179-187
[4]  
CHURCHILL SW, 1977, CHEM ENG-NEW YORK, V84, P91
[5]  
CHURCHILL SW, 1975, INT J HEAT MASS TRAN, V18, P1323, DOI [10.1016/0017-9310(75)90243-4, 10.1016/0017-9310(75)90222-7]
[6]  
GNIELINSKI V, 1976, INT CHEM ENG, V16, P359
[7]  
Grnnerud R., 1979, INVESTIGATION LIQU 4
[8]  
JSRAE, 2018, JSRAE TECHN BOOK SER, P6
[9]   A GENERAL CORRELATION FOR SATURATED 2-PHASE FLOW BOILING HEAT-TRANSFER INSIDE HORIZONTAL AND VERTICAL TUBES [J].
KANDLIKAR, SG .
JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 1990, 112 (01) :219-228
[10]   Effects of flash gas generation at the expansion device inlet on the dynamic characteristics of a refrigeration system [J].
Kang, Hoon ;
Joo, Youngju ;
Kim, Yonchan .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2008, 31 (03) :396-403