Development and evaluation of power system fault location scheme using practical fault data

被引:1
作者
Yoshimura, K. [1 ]
Tsutsumi, Y. [1 ]
Suetsugu, Y. [1 ]
Kihara, H. [1 ]
Ide, T. [1 ]
机构
[1] Cent Res Inst Elect Power Ind, 2-11-1 Iwado Kita, Komae, Tokyo 2018511, Japan
来源
2006 IEEE/PES POWER SYSTEMS CONFERENCE AND EXPOSITION. VOLS 1-5 | 2006年
关键词
electric power system; fault current; fault location; power quality; voltage measurement; voltage sag;
D O I
10.1109/PSCE.2006.296158
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This paper presents a new scheme of fault location on power system comparing actual measurements of voltage sag to fault current calculation results. Using a two-circuit transmission line fault analysis tool developed by CRIEPI*(1) for calculating voltage sag value, this scheme can locate a faulted point not depending on causes of the faults. By estimating fault point impedance, highly accurate fault location is expected. From a viewpoint of practical use, the presented scheme is applied to a real power system model of a Japanese electric power company using practical voltage sag measurement values at substations on subtransmission system. Results of this evaluation show that this scheme has a possibility of having practical accuracy of the fault location.
引用
收藏
页码:1637 / +
页数:2
相关论文
共 5 条
[1]  
INO T, 2002, OR253
[2]  
MORI R, P 2004 INT C EL ENG, P721
[3]  
MORI R, P 2004 NAT M REC IEE, P263
[4]  
TANAKA K, P 2002 ANN C POW EN
[5]  
1990, COUNTERMEASURE INSTA, V46, P16