Modeling of German Low Voltage Cables with Ground Return Path

被引:11
|
作者
Geis-Schroer, Johanna [1 ]
Hubschneider, Sebastian [1 ]
Held, Lukas [1 ]
Gielnik, Frederik [1 ]
Armbruster, Michael [2 ]
Suriyah, Michael [1 ]
Leibfried, Thomas [1 ]
机构
[1] Karlsruhe Inst Technol, Inst Elect Energy Syst & High Voltage Technol IEH, D-76137 Karlsruhe, Germany
[2] Stadtwerke Buehl GmbH, D-77815 Buehl, Germany
关键词
distribution systems; multiphase and unbalanced analysis; low voltage grids; low voltage cable; ground return path; asymmetric modeling;
D O I
10.3390/en14051265
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
In this contribution, measurement data of phase, neutral, and ground currents from real low voltage (LV) feeders in Germany is presented and analyzed. The data obtained is used to review and evaluate common modeling approaches for LV systems. An alternative modeling approach for detailed cable and ground modeling, which allows for the consideration of typical German LV earthing conditions and asymmetrical cable design, is proposed. Further, analytical calculation methods for model parameters are described and compared to laboratory measurement results of real LV cables. The models are then evaluated in terms of parameter sensitivity and parameter relevance, focusing on the influence of conventionally performed simplifications, such as neglecting house junction cables, shunt admittances, or temperature dependencies. By comparing measurement data from a real LV feeder to simulation results, the proposed modeling approach is validated.
引用
收藏
页数:34
相关论文
共 50 条
  • [21] A closed-form approximation for ground return impedance of underground cables
    Saad, O
    Gaba, G
    Giroux, M
    IEEE TRANSACTIONS ON POWER DELIVERY, 1996, 11 (03) : 1536 - 1545
  • [22] Influence of aging on polarization currents and return voltage measured in PILC cables
    Crine, JP
    Bucholz, V
    Colwell, M
    Cherukupalli, S
    Bernstein, BS
    2001 ANNUAL REPORT CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, 2001, : 188 - 191
  • [23] LOCALIZATION OF FAULTS IN LOW-VOLTAGE CABLES
    不详
    NATURE, 1945, 156 (3955) : 201 - 201
  • [24] SUSPENSION DEVICE PROTECTS LOW VOLTAGE CABLES
    MALMBORG, BD
    DESIGN NEWS, 1970, 25 (08) : 48 - +
  • [25] Research on the Coupling between High-voltage Cables and Low-voltage Cables in Electric Vehicles
    Wang, Huihui
    Gao, Changsheng
    Han, Hongji
    Ren, Jie
    Zhang, Dan
    2023 INTERNATIONAL CONFERENCE ON ELECTROMAGNETICS IN ADVANCED APPLICATIONS, ICEAA, 2023, : 273 - 276
  • [26] Effect of ground return path on partial discharge signal propagation along single-core and three-core power cables
    Li, Yan
    Wu, Lei
    Wouters, Peter A. A. F.
    Wagenaars, Paul
    van der Wielen, Peter C. J. M.
    Steennis, E. Fred
    INTERNATIONAL TRANSACTIONS ON ELECTRICAL ENERGY SYSTEMS, 2016, 26 (08): : 1783 - 1798
  • [27] HFC network return path performance modeling
    Krolikowski, Rafal
    PRZEGLAD ELEKTROTECHNICZNY, 2011, 87 (08): : 248 - 252
  • [28] Protection of Low-Voltage Plastic Cables by Low-Voltage Hihg-Power Fuses in Accordance with the German Standard VDE 0636.
    Gantz, Peter
    Elektrizitaetswirtschaft, 1977, 76 (20): : 704 - 707
  • [29] Wearable Measurement Method for Voltage to Ground of Conducted Noise on Unshielded Cables
    Arai, Naruto
    Okamoto, Ken
    Kato, Jun
    PROCEEDINGS OF THE 2020 INTERNATIONAL SYMPOSIUM ON ELECTROMAGNETIC COMPATIBILITY (EMC EUROPE), 2020,
  • [30] Study to evaluate the life of low voltage cables (II)
    Research Inst for Advanced Science, and Technology
    Bulletin of the University of Osaka Prefecture, Series A Engineering and Natural Sciences, 1996, 45 (02): : 65 - 70