Application of signal processing and analysis in detecting single line-to-ground (SLG) fault location in high-impedance grounded distribution network

被引:38
作者
Li, Yajie [1 ]
Meng, Xiaoli [1 ]
Song, Xiaohui [1 ]
机构
[1] China Elect Power Res Inst, Dept Distribut Network, Beijing 100192, Peoples R China
基金
中国国家自然科学基金;
关键词
Fault detection - Clustering algorithms - Reliability analysis - Electric power distribution - Impulse response;
D O I
10.1049/iet-gtd.2015.0555
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In high-impedance grounded distribution networks which are common in many countries, single line-to-ground (SLG) fault diagnosis is difficult due to weak fault characteristics, noise interference, three-phase unbalanced operation's influence and so on. Upon thorough analysis on the space-time characteristics of SLG fault, this study applies signal processing and analysis techniques to do SLG fault location detection. First, finite impulse response (FIR) filter is applied to effectively strain out interference factors and extract pure fault characteristics for each line. Afterwards, hierarchical clustering is used to classify lines based on the extracted fault characteristics. According to the clustering result, the fault line could be determined. If there are monitoring terminals distributed in the fault line, the fault section could also be further identified. Simulation shows that the proposed method works well under various fault conditions and has a higher reliability compared with wavelet analysis. Besides, this method makes full use of the existing hardware conditions in the grid and the cost is low, hence it has high practical value.
引用
收藏
页码:382 / 389
页数:8
相关论文
共 11 条
[1]  
[Anonymous], 2010, IEEE T POWER DELIV
[2]  
[Anonymous], 2011, CLUSTER ANAL
[3]  
[Anonymous], 1997, P CSEE
[4]   High-resistance ground retrofits in pulp and paper mills [J].
Beltz, R ;
Peacock, I ;
Vilcheck, W .
IEEE INDUSTRY APPLICATIONS MAGAZINE, 2001, 7 (02) :19-27
[5]   Accurate fault location technique for distribution system using fault-generated high-frequency transient voltage signals [J].
Bo, ZQ ;
Weller, G ;
Redfern, MA .
IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 1999, 146 (01) :73-79
[6]   Application of wavelet fuzzy neural network in locating single line to ground fault (SLG) in distribution lines [J].
Fan Chunju ;
Li, K. K. ;
Chan, W. L. ;
Yu Weiyong ;
Zhang Zhaoning .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2007, 29 (06) :497-503
[7]  
Jia Qing-quan, 2001, Proceedings of the CSEE, V21, P78
[8]   Single line-to-ground fault location based on unsynchronized phasors in automated ungrounded distribution systems [J].
Nam, Soon-Ryul ;
Kang, Sang-Hee ;
Ahn, Seon-Ju ;
Choi, Joon-Ho .
ELECTRIC POWER SYSTEMS RESEARCH, 2012, 86 :151-157
[9]  
Sanjit K. M., 2000, DIGITAL SIGNAL PROCE
[10]   Location strategies and evaluation of detection algorithms for earth faults in compensated MV distribution systems [J].
Welfonder, T ;
Leitloff, V ;
Feuillet, R ;
Vitet, S .
IEEE TRANSACTIONS ON POWER DELIVERY, 2000, 15 (04) :1121-1128