Characteristics and Restraining Method of Fast Transient Inrush Fault Currents in Synchronverters

被引:192
作者
Shuai, Zhikang [1 ]
Huang, Wen [1 ]
Shen, Chao [1 ]
Ge, Jun [1 ]
Shen, Z. John [2 ]
机构
[1] Hunan Univ, Coll Elect & Informat Engn, Changsha 410082, Hunan, Peoples R China
[2] IIT, Dept Elect Aand Comp Engn, Chicago, IL 60616 USA
关键词
Control strategy; inrush current; symmetrical fault; synchronverter; voltage drop; INVERTERS; SYNCHRONIZATION; CONVERTER;
D O I
10.1109/TIE.2017.2652362
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
Large transient inrush fault current in a synchronverter during a short-circuit fault can potentially damage the inverter and cause grid instability. It is therefore important to study the characteristics of and the way to restrain the inrush fault current. This paper investigates the characteristics of the synchronverter inrush fault current and proposes a new control method based on mode switching to protect synchronverters. First, an ideal voltage source inverter instantaneous inrush current calculation method for a grid symmetrical short circuit is discussed. Then, based on the inertia of synchronverter, the approximate calculation of the synchronverter instantaneous inrush current is described. The results show that the synchronverter's inrush current mainly consists of a gradually attenuated periodic component and a dc component when the phased voltage symmetry is lost. In our proposed new control approach, the synchronverter switches to the hysteresis controller to limit the output current quickly while staying connected to the grid, and supporting the grid voltage simultaneously. Simulation and experiment results verify the validity of the theoretical analysis.
引用
收藏
页码:7487 / 7497
页数:11
相关论文
共 24 条
[1]  
[Anonymous], 2000, OVERVIEW POWER QUALI
[2]   Synchronverter-Based Emulation and Control of HVDC Transmission [J].
Aouini, Raouia ;
Marinescu, Bogdan ;
Ben Kilani, Khadija ;
Elleuch, Mohamed .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2016, 31 (01) :278-286
[3]   Energy Management in Autonomous Microgrid Using Stability-Constrained Droop Control of Inverters [J].
Barklund, E. ;
Pogaku, Nagaraju ;
Prodanovic, Milan ;
Hernandez-Aramburo, C. ;
Green, Tim C. .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2008, 23 (05) :2346-2352
[4]   Overview of control and grid synchronization for distributed power generation systems [J].
Blaabjerg, Frede ;
Teodorescu, Remus ;
Liserre, Marco ;
Timbus, Adrian V. .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2006, 53 (05) :1398-1409
[5]   Novel adaptive hysteresis band modulation strategy for three-phase inverters [J].
Bowes, SR ;
Grewal, S ;
Holliday, D .
IEE PROCEEDINGS-ELECTRIC POWER APPLICATIONS, 2001, 148 (01) :51-61
[6]   Active and Reactive Power Strategies With Peak Current Limitation for Distributed Generation Inverters During Unbalanced Grid Faults [J].
Camacho, Antonio ;
Castilla, Miguel ;
Miret, Jaume ;
Borrell, Angel ;
Garcia de Vicuna, Luis .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2015, 62 (03) :1515-1525
[7]  
Dai X., 2009, PROC 2009 INT C SUST, P1
[8]   Analysis, Design, and Implementation of Virtual Impedance for Power Electronics Interfaced Distributed Generation [J].
He, Jinwei ;
Li, Yun Wei .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2011, 47 (06) :2525-2538
[9]  
IEEE Application Guide for IEEE Std 1547( TM), 2009, IEEE Standard 1547. 2- 2008, P1
[10]   Voltage Sag Compensation of Point of Common Coupling (PCC) Using Fault Current Limiter [J].
Jafari, M. ;
Naderi, S. B. ;
Hagh, M. Tarafdar ;
Abapour, M. ;
Hosseini, S. H. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2011, 26 (04) :2638-2646