Investigation of the performance of a cylindrical PCM-to-air heat exchanger (PAHE) for free ventilation cooling in fluctuating ambient environments

被引:22
作者
Yang, Dong [1 ,2 ]
Shi, Rui [1 ,2 ]
Wei, Haibin [1 ,2 ]
Du, Jinhui [1 ,2 ]
Wang, Jilibo [1 ,2 ]
机构
[1] Chongqing Univ, Sch Civil Engn, Chongqing 400044, Peoples R China
[2] Natl Ctr Int Res Low Carbon & Green Bldg, Chongqing 400044, Peoples R China
基金
中国国家自然科学基金;
关键词
Phase change material; Free cooling; Fluctuating thermal environment; Latent heat transfer; Peak temperature shaving; Cooling load reduction; PHASE-CHANGE MATERIAL; THERMAL PERFORMANCE; BUILDINGS; STORAGE; TECHNOLOGIES; COMFORT; WALL; INTEGRATION; SIMULATION; REDUCTION;
D O I
10.1016/j.scs.2019.101764
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
This paper proposes the use of a cylindrical annulus composed of phase change material (PCM), referred to as a PCM-air heat exchanger (PAHE), to regulate the supplied air temperature in ventilated buildings exposed to fluctuating thermal environments. The forced convection inside the PAHE tube enhances the heat transfer between the air and PCM, and thus both the sensible and latent heat transfer contribute to reducing the air temperature fluctuations and peak cooling/heating loads. Both experiments and numerical simulations are performed to investigate the performance of a PAHE exposed to fluctuating ambient temperatures. The effects of three PAHE parameters, i.e., the flow rate through the PAHE tube, melting temperature of the PCM, external diameter of the PAHE, and the tube length on the PAHE performance were investigated numerically. Maintaining a stable inner surface temperature in the PAHE is crucial for maximizing its ability to reduce air temperature fluctuation amplitude. For this purpose, these key parameters should be appropriately selected. The cooling performance of the PAHE in a region with hot summers and cold winters region was evaluated. The simulation incorporated real meteorological data of two transitional seasons and a summer, and demonstrated a maximum reduction in air temperature of 5.4 degrees C.
引用
收藏
页数:11
相关论文
共 35 条
  • [31] Experimental assessment on the use of phase change materials (PCMs)-bricks in the exterior wall of a full-scale room
    Wang, Xu
    Yu, Hang
    Li, Lu
    Zhao, Mei
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2016, 120 : 81 - 89
  • [32] Coupling of earth-to-air heat exchangers and buoyancy for energy efficient ventilation of buildings considering dynamic thermal behavior and cooling/heating capacity
    Wei, Haibin
    Yang, Dong
    Guo, Yuanhao
    Chen, Mengqian
    [J]. ENERGY, 2018, 147 : 587 - 602
  • [33] Numerical Investigation of Indoor Air Temperature with the Application of PCM Gypsum Board as Ceiling Panels in Buildings.
    Yahaya, N. A.
    Ahmad, H.
    [J]. 2ND INTERNATIONAL BUILDING CONTROL CONFERENCE, 2011, 20
  • [34] A demand-oriented approach for integrating earth-to-air heat exchangers into buildings for achieving year-round indoor thermal comfort
    Yang, Dong
    Wei, Haibin
    Shi, Rui
    Wang, Jilibo
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2019, 182 : 95 - 107
  • [35] Evaluation of the thermal performance of an earth-to-air heat exchanger (EAHE) in a harmonic thermal environment
    Yang, Dong
    Guo, Yuanhao
    Zhang, Jinpeng
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2016, 109 : 184 - 194