Effects of diffuser orifice plate on the performance of air-cooled steam condenser

被引:18
|
作者
Zhang, Xuelei [1 ]
Wu, Tingting [1 ]
机构
[1] North China Elect Power Univ, Sch Energy Power & Mech Engn, Baoding 071003, Peoples R China
关键词
Air-cooled steam condenser; Ambient wind; Diffuser orifice plate; Numerical simulation; WIND; FLOW;
D O I
10.1016/j.applthermaleng.2015.12.018
中图分类号
O414.1 [热力学];
学科分类号
摘要
Ambient wind has adverse impacts on the thermal-flow performances of ACSC. In this paper, a new measure to improve ACSC performance is proposed by installing diffuser orifice plate under the ACSC platform. As ambient wind flowing through diffuser hole in the plate, the velocity head converts to the pressure head, which contributes to shrink the negative pressure region under the ACSC platform and further improve ACSC performance. The numerical model of Column 4 section in a 600 MW ACSC is investigated, and the results show that under windy conditions, the diffuser orifice plate not only increases the volume flows across almost all fans due to the shrinkage of the negative pressure zone, but decreases fans' inlet air temperatures, especially for upstream fans. At a wind speed of 9 m/s, the volumetric effectiveness of windward Fan(1,4) is increased by 19.9%, and the temperature drop at windward Fan(1,4) inlet is 1.1K, as considering diffuser orifice plate. Moreover, a more uniform flow field distribution such as pressure, temperature as well as air flow rate can form via diffuser orifice plate, which may also improve heat transfer of condenser cell. At a wind speed of 9 m/s, the heat transfer effectiveness is increased by 6.6 percent points. The numerical results indicate that diffuser orifice plate is an effective way to restrain the adverse impacts of ambient wind, and it can be beneficial to operation improvement of the direct dry cooling systems in power plants. (C) 2015 Elsevier Ltd. All rights reserved.
引用
收藏
页码:179 / 188
页数:10
相关论文
共 50 条
  • [1] Wind effects on air-cooled condenser performance
    Borghei, Leila
    Khoshkhoo, Ramin Haghighi
    NEW ASPECTS OF FLUID MECHANICS, HEAT TRANSFER AND ENVIRONMENT, 2010, : 193 - +
  • [2] Performance Forecast of Air-Cooled Steam Condenser under Windy Conditions
    Zhang, Xuelei
    Chen, Haiping
    JOURNAL OF ENERGY ENGINEERING, 2016, 142 (01)
  • [3] Performance prediction of an air-cooled steam condenser using UDF method
    He, W. F.
    Dai, Y. P.
    Wang, J. F.
    Li, M. Q.
    Ma, Q. Z.
    APPLIED THERMAL ENGINEERING, 2013, 50 (01) : 1339 - 1350
  • [4] Performance Assessment of Air-Cooled Steam Condenser with Guide Vane Cascade
    ZHANG Xuelei
    LI Yunpeng
    CHEN Haiping
    JournalofThermalScience, 2019, 28 (05) : 993 - 1003
  • [5] Performance Assessment of Air-Cooled Steam Condenser with Guide Vane Cascade
    Xuelei Zhang
    Yunpeng Li
    Haiping Chen
    Journal of Thermal Science, 2019, 28 : 993 - 1003
  • [6] Performance trends of an air-cooled steam condenser under windy conditions
    van Rooyen, J. A.
    Kroger, D. G.
    JOURNAL OF ENGINEERING FOR GAS TURBINES AND POWER-TRANSACTIONS OF THE ASME, 2008, 130 (02):
  • [7] Performance Assessment of Air-Cooled Steam Condenser with Guide Vane Cascade
    Zhang Xuelei
    Li Yunpeng
    Chen Haiping
    JOURNAL OF THERMAL SCIENCE, 2019, 28 (05) : 993 - 1003
  • [8] THE EFFECT OF HUB CONFIGURATION ON THE PERFORMANCE OF AN AIR-COOLED STEAM CONDENSER FAN
    Meiring, Z.
    van der Spuy, S. J.
    Meyer, C. J.
    PROCEEDINGS OF THE ASME TURBO EXPO 2020: TURBOMACHINERY TECHNICAL CONFERENCE AND EXPOSITION, VOL 1, 2020,
  • [9] NUMERICAL STUDY ON HEAT -TRANSFER PERFORMANCE OF PLATE AIR-COOLED CONDENSER
    Huang, X. Q.
    Zhang, X.
    7TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATING AND AIR CONDITIONING, PROCEEDINGS OF ISHVAC 2011, VOLS I-IV, 2011, : 1353 - 1359
  • [10] Air-cooled condenser
    Phogat, S.S.