Sensitivity of transformer's hottest-spot and equivalent aging to selected parameters

被引:48
作者
Peterchuck, D [1 ]
Pahwa, A
机构
[1] Omaha Publ Power Dist, Substn Dept, Elkhorn, NE 68022 USA
[2] Kansas State Univ, Dept Elect & Comp Engn, Manhattan, KS 66506 USA
基金
美国国家科学基金会;
关键词
insulation aging; Monte Carlo methods; power transformer; transformer windings;
D O I
10.1109/TPWRD.2002.803708
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In 1995, IEEE released a revised Transformer Loading Guide which includes an Annex G that contains an additional set of transformer temperature equations that incorporate oil-flow phenomena, changing ambient air temperature, and account for the change in resistivity of the winding due to heating. These new equations. involve empirical exponent variables that account for properties of the transformer. This paper investigates sensitivity of hottest-spot temperature and equivalent aging of transformers with respect to these variables. By varying these variables,under various load conditions and by Monte Carlo simulation with different probability distributions of these variables, their importance in the transformer model and their influence in modeling accuracy pertaining to the Annex G equations have been obtained.
引用
收藏
页码:996 / 1001
页数:6
相关论文
共 6 条
[1]  
*ANSI IEEE, C57911995 ANSIIEEE
[2]   EFFECT OF OIL VISCOSITY ON TRANSFORMER LOADING CAPABILITY AT LOW AMBIENT-TEMPERATURES [J].
AUBIN, J ;
PIERCE, LW ;
LANGHAME, Y .
IEEE TRANSACTIONS ON POWER DELIVERY, 1992, 7 (02) :516-524
[3]  
PETERCHUCK D, 2000, THESIS KANSAS STATE
[4]   PREDICTING LIQUID-FILLED TRANSFORMER LOADING CAPABILITY [J].
PIERCE, LW .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1994, 30 (01) :170-178
[5]   AN INVESTIGATION OF THE THERMAL PERFORMANCE OF AN OIL FILLED TRANSFORMER WINDING [J].
PIERCE, LW ;
MCNUTT, WJ .
IEEE TRANSACTIONS ON POWER DELIVERY, 1992, 7 (03) :1347-1358
[6]  
WOODCOCK D, 1997, ELEC LIGHT POWER, V75, P23