Determination of Optimal Converter Operating Points Regarding Static Voltage Stability and System Losses in Hybrid Transmission Systems

被引:0
作者
Bennewitz, Florian [1 ]
Weck, Sebastian [1 ]
Hannappel, Johannes [1 ]
Hanson, Jutta [1 ]
机构
[1] Tech Univ Darmstadt, Dept Elect Power Supply Integrat Renewable Energi, Darmstadt, Germany
来源
2017 11TH IEEE INTERNATIONAL CONFERENCE ON COMPATIBILITY, POWER ELECTRONICS AND POWER ENGINEERING (CPE-POWERENG) | 2017年
关键词
hybrid transmission system; overlay DC system; voltage source converters; static voltage stability; reactive power;
D O I
10.1109/CPE.2017.7915138
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The transition of the European electrical energy system leads to rising installations of renewable energy sources (RES). Average transmission distances and active and reactive power losses increase, because RES are mainly installed at sites with a high yield of primary energy. This development affects the voltage stability of the system. To address these challenges, a meshed high voltage direct current (HVDC) overlay system might be used. Within this publication an optimization algorithm is proposed to determine optimal converter operating points. Thereby an iterative load flow approach determines voltage stability limit. A 58 AC busbar transmission system is used where 9 converters are applied forming a HVDC overlay system. Results show that the optimization approach is able to determine optimal operating points regarding static voltage stability as well as regarding overall system losses.