Performance testing of a cross-flow membrane-based liquid desiccant dehumidification system

被引:45
作者
Bai, Hongyu [1 ]
Zhu, Jie [1 ]
Chen, Ziwei [1 ]
Ma, Lina [1 ]
Wang, Ruzhu [2 ]
Li, Tingxian [2 ]
机构
[1] Univ Nottingham, Dept Architecture & Built Environm, Univ Pk, Nottingham NG7 2RD, England
[2] Shanghai Jiao Tong Univ, Inst Refrigerat & Cryogen, Key Lab Power Machinery & Engn MOE, Dongchuan Rd 800, Shanghai 200240, Peoples R China
关键词
Liquid desiccant; Membrane-based; Dehumidification; Performance testing; Effectiveness; MASS-TRANSFER; AIR DEHUMIDIFICATION; TUBE BANK; HEAT; EXCHANGER; SINGLE; MODEL;
D O I
10.1016/j.applthermaleng.2017.03.058
中图分类号
O414.1 [热力学];
学科分类号
摘要
A membrane-based liquid desiccant dehumidification system is one of high energy efficient dehumidification approaches, which allows heat and moisture transfers between air stream and desiccant solution without carryover problem. The system performance is investigated experimentally with calcium chloride, and the impacts of main operating parameters on dehumidification effectiveness (i.e. sensible, latent and total effectiveness) are evaluated, which include dimensionless parameters (i.e. solution to air mass flow rate ratio m* and number of heat transfer units NTU) and solution properties (i.e. concentration col and inlet temperature T-sol,T-in). The sensible, latent and total effectiveness reach the maximum values of 0.49, 0.55, and 0.53 respectively at m* = 3.5 and NTU = 12, and these effectiveness are not limited by m* and NTU when m* > 2 and NTU > 10. Both the latent and total effectiveness increase with C-sol, while almost no variation is observed in the sensible effectiveness. All effectiveness can be improved by decreasing T-sol,T-in. The experimental data provide a full map of main design parameters for the membrane-based liquid desiccant air conditioning technology. (C) 2017 Elsevier Ltd. All rights reserved.
引用
收藏
页码:119 / 131
页数:13
相关论文
共 51 条
[1]   Performance analysis of a membrane liquid desiccant air-conditioning system [J].
Abdel-Salam, Ahmed H. ;
Ge, Gaoming ;
Simonson, Carey J. .
ENERGY AND BUILDINGS, 2013, 62 :559-569
[2]   State-of-the-art in liquid-to-air membrane energy exchangers (LAMEEs): A comprehensive review [J].
Abdel-Salam, Mohamed R. H. ;
Ge, Gaoming ;
Fauchoux, Melanie ;
Besant, Robert W. ;
Simonson, Carey J. .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2014, 39 :700-728
[3]  
[Anonymous], 2013, 2013 ASHRAE Handbook Fundamentals
[4]  
[Anonymous], 2013, 842013 ANSIASHRAE
[5]  
[Anonymous], ENCY ENERGY
[6]   AN ANALYTIC CORRELATION FOR THE VAPOR-PRESSURE OF AQUEOUS AND NONAQUEOUS SOLUTIONS OF SINGLE AND MIXED ELECTROLYTES .2. APPLICATION AND EXTENSION [J].
CISTERNAS, LA ;
LAM, EJ .
FLUID PHASE EQUILIBRIA, 1991, 62 (1-2) :11-27
[7]   Use of liquid desiccant cooling to improve the performance of vapor compression air conditioning [J].
Dai, YJ ;
Wang, RZ ;
Zhang, HF ;
Yu, JD .
APPLIED THERMAL ENGINEERING, 2001, 21 (12) :1185-1202
[8]   Desiccant cooling air conditioning: a review [J].
Daou, K ;
Wang, RZ ;
Xia, ZZ .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2006, 10 (02) :55-77
[9]  
Erb B., 2009, THESIS
[10]  
Fan H., 2005, THESIS