Dynamic prediction of the pre-dehumidification of a radiant floor cooling and displacement ventilation system based on computational fluid dynamics and a back-propagation neural network: A case study of an office room

被引:14
作者
Su, Meng [1 ]
Liu, Jiying [1 ,2 ]
Zhou, Shiyu [1 ]
Miao, Jikui [3 ]
Kim, Moon Keun [4 ]
机构
[1] Shandong Jianzhu Univ, Sch Thermal Engn, 1000 Fengming Rd, Jinan 250101, Peoples R China
[2] Shandong GRAD Grp, Built Environm Design & Res Inst, Dezhou, Peoples R China
[3] Shandong Jianzhu Univ, Sch Architecture & Urban Planning, Jinan, Peoples R China
[4] Oslo Metropolitan Univ, Dept Civil Engn & Energy Technol, Oslo, Norway
关键词
Floor condensation; Radiant floor cooling; Displacement ventilation; Computational fluid dynamics; Pre-dehumidification; Back-propagation neural network; RELATIVE-HUMIDITY; CEILING PANEL; HEAT-PUMP; CONDENSATION; PERFORMANCE; ENVIRONMENT; TEMPERATURE; DESIGN;
D O I
10.1177/1420326X221107110
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
This study was carried out to solve the problem of condensation in radiant floor cooling systems. Computational fluid dynamics simulation and back-propagation neural network prediction were employed to conduct thorough research to predict the effects of the displacement ventilation dehumidification phase in an office building located in Jinan, China. The effects of the air supply temperature (T- as ), air supply flow rate (V- as ), air supply humidity ratio (H- as ), floor temperature (T- floor ), initial indoor temperature (T- ini ) and relative humidity (H- ini ) on the duration and energy consumption of pre-dehumidification were investigated. The big data show the air dew point temperature (T- ad ) produced the most significant effect on the pre-dehumidification duration and energy consumption, while T- as would cause the least significant effect. With the decrease of T- ad , the pre-dehumidification duration and energy consumption were, respectively, decreased by 59.1% and 44.2%. Furthermore, with the variation of V- as , the energy consumption exhibited a fluctuating trend. This study provides a novel and effective method to assess the pre-dehumidification control of radiant floor surfaces by considering different initial indoor conditions and air supply parameters.
引用
收藏
页码:2386 / 2410
页数:25
相关论文
共 60 条
[1]  
[Anonymous], 2019, news release
[2]  
[Anonymous], 2018, Ministry of Housing and Urban-Rural Development of the People's Republic of China
[3]   Energy efficient room air distribution [J].
Awbi, HB .
RENEWABLE ENERGY, 1998, 15 (1-4) :293-299
[4]  
Cengel A, 2003, Heat Transfer, A Practical Approach
[5]   COMPARISON OF DIFFERENT K-EPSILON MODELS FOR INDOOR AIR-FLOW COMPUTATIONS [J].
CHEN, Q .
NUMERICAL HEAT TRANSFER PART B-FUNDAMENTALS, 1995, 28 (03) :353-369
[6]   Fast simulation and high-fidelity reduced-order model of the multi-zone radiant floor system for efficient application to model predictive control [J].
Chen, Qiong ;
Li, Nan .
ENERGY AND BUILDINGS, 2021, 248
[7]   Application of adaptive predictive control to a floor heating system with a large thermal lag [J].
Chen, TY .
ENERGY AND BUILDINGS, 2002, 34 (01) :45-51
[8]  
Davidson Lars., 2018, An introduction to turbulence models"
[9]   POD reduced-order unstructured mesh modeling applied to 2D and 3D fluid flow [J].
Du, J. ;
Fang, F. ;
Pain, C. C. ;
Navon, I. M. ;
Zhu, J. ;
Ham, D. A. .
COMPUTERS & MATHEMATICS WITH APPLICATIONS, 2013, 65 (03) :362-379
[10]   Testing and modelling of a novel ceiling panel for maintaining space relative humidity by moisture transfer [J].
Fauchoux, Melanie ;
Bansal, Mohit ;
Talukdar, Prabal ;
Simonson, Carey J. ;
Torvi, David .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2010, 53 (19-20) :3961-3968