Defining the cooling and heating solar efficiency of a building component skin: application to a modular living wall

被引:11
作者
Azkorra-Larrinaga, Z. [1 ]
Erkoreka-Gonzalez, A. [1 ]
Flores-Abascal, I [1 ]
Perez-Iribarren, E. [1 ]
Romero-Anton, N. [1 ]
机构
[1] Univ Basque Country UPV EHU, Dept Energy Engn, ENEDI Res Grp, Alda Urquijo S-N, Bilbao 48013, Spain
关键词
Cooling efficiency; Energy performance; Energy saving; Modular Living Wall; GREEN ROOFS; ENERGY SIMULATION; THERMAL-BEHAVIOR; URBAN; TEMPERATURE; PERFORMANCE; SYSTEMS; PREDICTION; FRAMEWORK; DESIGN;
D O I
10.1016/j.applthermaleng.2022.118403
中图分类号
O414.1 [热力学];
学科分类号
摘要
The thermal evaluation of building components composed of a base wall with a solar passive skin solution, such as a vertical/roof greenery system, ventilated facade, reflective painting, etc., is usually performed as a whole. In this research, it has been proven that, independently of the base wall thermal inertia and insulation level, the temperature of the outermost surface layer of any building component during sunny hours is mainly dependent on the ambient air temperature and relative humidity, the incident global solar radiation and the building skin behaviour. The latter assumption has been proven on the south wall of a reference building simulated with TRNSYS. The south wall properties have been varied and the building has been subjected to different climates. The assumption's validity has been checked for twelve south wall cases: a combination of 2 thermal transmittance, 2 thermal inertia and 3 climates. Each case has been simulated for a whole year. Based on this finding and the local ambient conditions for sunny hours, the hypothetical achievable maximum and minimum temperatures for the outermost surface layer have been defined. Then, based on the outermost surface temperature experimental measurements, the cooling and heating solar efficiencies valid for any skin solution have been defined. Furthermore, the developed methodology has been applied to a vertical living wall tested for a whole year under the accuracy and quality procedure of the PASLINK method. In this way, the cooling and heating solar efficiencies were experimentally determined for this skin solution for both, the hot cold seasons. The study has shown that the cooling efficiency during the hot season is 90.8%. As expected, even during sunny summer hours, the presence of water positively affects the performance of the facade, as it brings the base wall external surface temperature close to the ambient wet bulb temperature, therefore reducing the cooling load of the building. For the cold season, the cooling efficiency was similar, at 90.3%, which means a heating efficiency of 9.7%. Again, even for sunny winter hours, the values of the external surface temperature tend towards the ambient air wet bulb temperature, resulting in an increase in the heating demand. These experimental efficiency values allow the heating or cooling behaviour of different skin solutions to be comparable with a single number that is independent of the base wall composition. In addition, independently of the base wall composition, once the experimental efficiency value of a given skin solution is known, it allows (during sunny hours) the base wall outermost surface temperature to be calculated with precision. The latter makes it possible to increase the accuracy of the estimation of the heating and cooling demands of such methods as the degree-day method.
引用
收藏
页数:16
相关论文
共 56 条
[1]   The concept of ecosystem services in adaptive urban planning and design: A framework for supporting innovation [J].
Ahern, Jack ;
Cilliers, Sarel ;
Niemela, Jari .
LANDSCAPE AND URBAN PLANNING, 2014, 125 :254-259
[2]   Developing a one-dimensional heat and mass transfer algorithm for describing the effect of green roofs on the built environment: Comparison with experimental results [J].
Alexandri, Eleftherla ;
Jones, Phil .
BUILDING AND ENVIRONMENT, 2007, 42 (08) :2835-2849
[3]  
[Anonymous], 2006, ROYAL DECREE 3142006
[4]  
[Anonymous], 1997, 6946 UNEEN ISO
[5]  
ASHRAE, 2005, FUND VOL ASHRAE HDB
[6]   An investigation of sensible heat fluxes at a green roof in a laboratory setup [J].
Ayata, Tahir ;
Tabares-Velasco, Paulo Cesar ;
Srebric, Jelena .
BUILDING AND ENVIRONMENT, 2011, 46 (09) :1851-1861
[7]   Evaluation of green walls as a passive acoustic insulation system for buildings [J].
Azkorra, Z. ;
Perez, G. ;
Coma, J. ;
Cabeza, L. F. ;
Bures, S. ;
Alvaro, J. E. ;
Erkoreka, A. ;
Urrestarazu, M. .
APPLIED ACOUSTICS, 2015, 89 :46-56
[8]   Towards measurement and verification of energy performance under the framework of the European directive for energy performance of buildings [J].
Burman, Esfand ;
Mumovic, Dejan ;
Kimpian, Judit .
ENERGY, 2014, 77 :153-163
[9]   Go greener, feel better? The positive effects of biodiversity on the well-being of individuals visiting, urban and peri-urban green areas [J].
Carrus, Giuseppe ;
Scopelliti, Massimiliano ;
Lafortezza, Raffaele ;
Colangelo, Giuseppe ;
Ferrini, Francesco ;
Salbitano, Fabio ;
Agrimi, Mariagrazia ;
Portoghesi, Luigi ;
Sernenzato, Paolo ;
Sanesi, Giovanni .
LANDSCAPE AND URBAN PLANNING, 2015, 134 :221-228
[10]   Dynamic integrated method applied to assessing the in-situ thermal performance of walls and whole buildings. Robustness analysis supported by a benchmark set-up [J].
Chavez, K. ;
Ruiz, D. P. ;
Jimenez, M. J. .
APPLIED THERMAL ENGINEERING, 2019, 152 :287-307