Effective suppression method of three-phase transformer's inrush current

被引:0
|
作者
Cheng, CL [1 ]
Lin, CE [1 ]
Hou, KC [1 ]
Hsia, YF [1 ]
机构
[1] Huwei Inst Technol, Dept Elect Engn, Yunlin, Taiwan
关键词
non-synchronous; inrush current; suppressing method; transformer;
D O I
暂无
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
Three-phase transformers are key components in power systems and power plants. Security, stability and increasing the life of transformers are important to system operation. When a three-phase transformer is energized, the inrush current - due to flux saturation in the core -results in a malfunction of the differential relay and also causes a stress impact to the transformer. These have an adverse effect on the security and stability of the power system. In this paper, a non-synchronous suppressing method is proposed to suppress the inrush current of three-phase transformers. The overvoltages caused by the inrush current can also be avoided. The proposed method is examined by means of experiments, which show excellent results in suppressing the inrush current. The proposed method can be applied to improve the protective relaying system of three-phase transformers.
引用
收藏
页码:2030 / 2033
页数:4
相关论文
共 50 条
  • [21] Transformer controlled switching to eliminate inrush current - Part II: Field tests on a 100MVA three-phase transformer
    Bronzeado, Herivelto S.
    Pinto, Servulo O.
    Jonsson, Per
    de Oliveira, Jos Carlos
    Chaves, Marcelo L. R.
    2006 IEEE/PES TRANSMISSION & DISTRIBUTION CONFERENCE & EXPOSITION: LATIN AMERICA, VOLS 1-3, 2006, : 1570 - +
  • [22] A study on numerical calculation of inrush current in three-phase transformers
    Tokunaga, Yoshitaka
    IEEJ Transactions on Power and Energy, 2013, 133 (07) : 579 - 586
  • [23] Inrush current mitigation in three-phase transformers with isolated neutral
    Cano-Gonzalez, Ramon
    Bachiller-Soler, Alfonso
    Antonio Rosendo-Macias, Jose
    Alvarez-Cordero, Gabriel
    ELECTRIC POWER SYSTEMS RESEARCH, 2015, 121 : 14 - 19
  • [24] Utilizing Preisach models of hysteresis in the computation of three-phase transformer inrush currents
    Adly, AA
    Hanafy, HH
    Abu-Shady, SE
    ELECTRIC POWER SYSTEMS RESEARCH, 2003, 65 (03) : 233 - 238
  • [25] Measurement Verification of a Developed Strategy of Inrush Current Reduction for a Non-Loaded Three-Phase Dy Transformer
    Lukaniszyn, Marian
    Majka, Lukasz
    Baron, Bernard
    Kulesz, Barbara
    Tomczewski, Krzysztof
    Wrobel, Krzysztof
    ENERGIES, 2024, 17 (21)
  • [26] Simulation Analysis of Inrush Current of Three Phase Transformer Based on MATLAB
    Song, Yundong
    Jia, Hongde
    Xu, Xiaofeng
    Yu, Li
    2017 29TH CHINESE CONTROL AND DECISION CONFERENCE (CCDC), 2017, : 3983 - 3985
  • [27] A Novel DC Current Injection Suppression Method for Three-Phase Grid-Connected Inverter Without the Isolation Transformer
    Chen, Min
    Xu, Dehong
    Zhang, Tao
    Shi, Keyan
    He, Guofeng
    Rajashekara, Kaushik
    IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2018, 65 (11) : 8656 - 8666
  • [28] Inrush Current Reduction Strategy for a Three-Phase Dy Transformer Based on Pre-Magnetization of the Columns and Controlled Switching
    Lukaniszyn, Marian
    Baron, Bernard
    Kolanska-Pluska, Joanna
    Majka, Lukasz
    ENERGIES, 2023, 16 (13)
  • [29] Simulation of three-phase transformer inrush currents by using backward and numerical differentiation formulae
    Tokic, Amir
    Milardic, Viktor
    Uglesic, Ivo
    Jukan, Admir
    ELECTRIC POWER SYSTEMS RESEARCH, 2015, 127 : 177 - 185
  • [30] An Isolated Three-Phase Three-Switch Buck Rectifier with Inrush Current Limiting
    Noroozi, N.
    Zolghadri, M. R.