Lessons Learned from Fire in Air Supply Ducts

被引:1
作者
Waller, Al [1 ]
Brown, Michelle [1 ]
机构
[1] FMC Corp, Philadelphia, PA 19103 USA
关键词
lessons learned; fire; HEPA filter; air filter; thermal inertia;
D O I
10.1002/prs.11661
中图分类号
TQ [化学工业];
学科分类号
0817 ;
摘要
In 2012, loss of air flow caused activation of interlocks to shut off steam and electrical heat inputs to an air heating system that was part of a drying/milling operation. Shortly thereafter, upstream filters and air ducts ignited causing more than US$500K in damage and business interruption. Investigations concluded that the interlocks functioned as designed on loss-of-airflow but were not sufficient to prevent overheating the inlet air filters (including HEPA filters) by the residual heat in the air heaters. The two main lessons learned from this fire incident apply to a broad range of operations in the chemical process industries (CPI): <list id="prs11661-list-0001" list-type="1"> <list-item id="prs11661-li-0001">Mundane unit operations such as air filters that have combustible components must be evaluated as thoroughly as the rest of the chemical process. <list-item id="prs11661-li-0002">Designers and PHA leaders must recognize the potential of thermal inertia of heaters (and coolers) to heat (or cool) a stagnant volume of fluid when flow is interrupted. Gas streams are particularly susceptible due to the low heat capacity relative to the heat capacity of a metallic heat exchanger. Interlocking the supplies (to steam and electrical heaters in this incident) is often necessary but may not be sufficient. Other lessons relearned include the importance of learning from a previous near miss, the importance of limiting escalation aspects of this fire, and the importance of preventative maintenance. (c) 2014 American Institute of Chemical Engineers Process Saf Prog, 2014
引用
收藏
页码:392 / 394
页数:3
相关论文
共 1 条
[1]  
Kletz T, 2009, WHAT WENT WRONG? CASE HISTORIES OF PROCESS PLANT DISASTERS AND HOW THEY COULD HAVE BEEN AVOIDED, 5TH EDITION, P1