Energy efficiency indicators for combined cooling, heating and power systems

被引:23
作者
Ma, Weiwu [1 ]
Fan, Jiaqian [1 ]
Fang, Song [2 ]
Hassan, N. M. S. [3 ]
Zhang, Yucong [1 ]
Wu, Xiaotian [1 ]
Li, Yi [1 ]
Hu, Rong [4 ]
Liu, Gang [1 ]
机构
[1] Cent South Univ, Sch Energy Sci & Engn, Changsha 410083, Peoples R China
[2] Zhejiang Univ, Inst Refrigerat & Cryogen, Hangzhou, Peoples R China
[3] Cent Queensland Univ, Sch Engn & Technol, Cairns, Qld 4870, Australia
[4] Guilin Univ Elect Technol, Sch Architecture & Traff Engn, Guangxi 541004, Peoples R China
基金
中国国家自然科学基金;
关键词
Combined cooling; Heating and power system; Primary energy rate; Primary energy saving rate; Average comprehensive energy utilization; efficiency; OPERATIONAL STRATEGY; CCHP SYSTEMS; PERFORMANCE; OPTIMIZATION; MODEL; DRIVEN;
D O I
10.1016/j.enconman.2021.114187
中图分类号
O414.1 [热力学];
学科分类号
摘要
Combined cooling, heating and power system is an effective technology for energy conservation and environmental protection, especially for buildings with multiple demands on electricity, cooling and heating load. Various energy indicators have been proposed for evaluating and optimizing the energy efficiency of combined cooling, heating and power systems, but previous studies have not yet clarified how to use them in a reasonable way that takes their specific merits into account. This paper aims to identify the underlying effects of three common energy indicators, including the primary energy rate, primary energy saving rate, and annual average comprehensive energy utilization efficiency, based on the optimized performance of combined cooling, heating and power systems with different typical configurations. This paper proposes three combined cooling, heating and power system configurations for an office building in Kunming to conduct a comparative analysis of three energy indicators. Two common operation strategy (the following thermal load and following electricity load) and the genetic algorithm are selected to performed single-objective optimization with energy indicator as target. The economic and environmental analysis is also carried out to show the impact of energy indicators on other indicators. The results show that, the indicators primary energy rate and primary energy saving rate have the same optimization effect of energy consumption when the system configuration and operation strategy are identical, as the difference between the primary energy rate values is not more than 1%, and the difference between the primary energy saving rate values is not more than 0.5%. The advantage of primary energy rate is that the difference between the primary energy rate values of combined cooling, heating and power systems and reference system could show whether carbon dioxide emissions are reduced, and the advantage of primary energy saving rate is that its value directly indicates whether the system achieves energy-saving or not. Furthermore, the annual average comprehensive energy utilization rate is not suitable for the single-objective optimization of combined cooling, heating and power systems. This study distinguishes the differences between indicators and the conclusions are of general significance which could provide valuable guidance for designers to select optimal energy indicators applying to the optimization design of combined cooling, heating and power systems.
引用
收藏
页数:13
相关论文
共 40 条
[1]  
[Anonymous], GB501892015
[2]  
[Anonymous], 1452010 CJJ
[3]   Energy and exergy analyses of a novel seasonal CCHP system driven by a gas turbine integrated with a biomass gasification unit and a LiBr-water absorption chiller [J].
Asgari, N. ;
Khoshbakhti, R. ;
Mirmasoumi, S. .
ENERGY CONVERSION AND MANAGEMENT, 2020, 220
[4]  
Beith R, 2011, WOODHEAD PUBL SER EN, P1
[5]   Combined cooling, heating and power: A review of performance improvement and optimization [J].
Cho, Heejin ;
Smith, Amanda D. ;
Mago, Pedro .
APPLIED ENERGY, 2014, 136 :168-185
[6]   Cooling, heating, and power energy performance for system feasibility [J].
Fumo, N. ;
Mago, P. J. ;
Chamra, L. M. .
PROCEEDINGS OF THE INSTITUTION OF MECHANICAL ENGINEERS PART A-JOURNAL OF POWER AND ENERGY, 2008, 222 (A4) :347-354
[7]   Emission operational strategy for combined cooling, heating, and power systems [J].
Fumo, Nelson ;
Mago, Pedro J. ;
Chamra, Louay M. .
APPLIED ENERGY, 2009, 86 (11) :2344-2350
[8]   Analysis of cooling, heating, and power systems based on site energy consumption [J].
Furno, Nelson ;
Mago, Pedro J. ;
Chamra, Louay M. .
APPLIED ENERGY, 2009, 86 (06) :928-932
[9]   An overview of optimization technologies applied in combined cooling, heating and power systems [J].
Gao, Lei ;
Hwang, Yunho ;
Cao, Tao .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2019, 114
[10]   Integrated assessment of combined cooling heating and power systems under different design and management options for residential buildings in Shanghai [J].
Gu, Qunyin ;
Ren, Hongbo ;
Gao, Weijun ;
Ren, Jianxing .
ENERGY AND BUILDINGS, 2012, 51 :143-152