Highly sensitive hydrogen sensors: Pd-coated Si nanowire arrays for detection of dissolved hydrogen in oil

被引:19
作者
Jang, Byungjin [1 ]
Kim, Min Hyung [1 ]
Baek, Jisun [1 ]
Kim, Wonkung [1 ]
Lee, Wooyoung [1 ]
机构
[1] Yonsei Univ, Dept Mat Sci & Engn, 262 Seongsanno, Seoul 129749, South Korea
来源
SENSORS AND ACTUATORS B-CHEMICAL | 2018年 / 273卷
基金
新加坡国家研究基金会;
关键词
Pd; Si nanowire arrays; Hydrogen gas sensor; Transformer; Transformer oil; TRANSFORMER OIL; GAS-ANALYSIS;
D O I
10.1016/j.snb.2018.06.111
中图分类号
O65 [分析化学];
学科分类号
070302 ; 081704 ;
摘要
We studied the H-2 sensing properties of Pd nanoparticles on vertical standing Si nanowire (NW) arrays for the detection of dissolved hydrogen (H-2) gas in transformer oil. The Pd-coated Si NW arrays were fabricated by using the aqueous electroless etching method and sputtering. The Pd-coated Si NW arrays were immersed and measured in transformer oil with various dissolved concentrations of H-2. We found that Pd-coated Si NW arrays showed significantly superior performance with regard to the response (similar to 1000%), the lowest detection limit (1 ppm), and the response time (600 s). The Pd-coated Si NW arrays showed a temperature coefficient of resistance (TCR) of 6.53 x 10(-3) degrees C-1 at various oil temperatures (20-80 degrees C). Pd-coated Si NW arrays showed good reliability for the detection of H-2 in oil at room temperature (20 degrees C), with nearly the same initial resistance for 30 days.
引用
收藏
页码:809 / 814
页数:6
相关论文
共 21 条
  • [1] [Anonymous], C57 IEEE
  • [2] High-performance hydrogen sensing properties and sensing mechanism in Pd-coated p-type Si nanowire arrays
    Baek, Jisun
    Jang, Byungjin
    Kim, Min Hyung
    Kim, Wonkung
    Kim, Jeongmin
    Rim, Hyun Jun
    Shin, Sera
    Lee, Taeyoon
    Cho, Sungmee
    Lee, Wooyoung
    [J]. SENSORS AND ACTUATORS B-CHEMICAL, 2018, 256 : 465 - 471
  • [3] MONITOR FOR HYDROGEN DISSOLVED IN TRANSFORMER OIL
    BELANGER, G
    DUVAL, M
    [J]. IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1977, 12 (05): : 334 - 340
  • [4] NIR and optical fiber sensor for gases detection produced by transformation oil degradation
    Benounis, M.
    Aka-Ngnui, T.
    Jaffrezic, N.
    Dutasta, J. P.
    [J]. SENSORS AND ACTUATORS A-PHYSICAL, 2008, 141 (01) : 76 - 83
  • [5] Thin palladium film as a sensor of hydrogen gas dissolved in transformer oil
    Bodzenta, J
    Burak, B
    Gacek, Z
    Jakubik, WP
    Kochowski, S
    Urbanczyk, M
    [J]. SENSORS AND ACTUATORS B-CHEMICAL, 2002, 87 (01) : 82 - 87
  • [6] DIND JE, 1975, PULP PAP-CANADA, V76, P61
  • [7] Duval M., 1989, IEEE Electrical Insulation Magazine, V5, P22, DOI 10.1109/57.44605
  • [8] COMPARISON OF PALLADIUM-SILVER AND PALLADIUM-YTTRIUM ALLOYS AS HYDROGEN SEPARATION MEMBRANES
    FORT, D
    FARR, JPG
    HARRIS, IR
    [J]. JOURNAL OF THE LESS-COMMON METALS, 1975, 39 (02): : 293 - 308
  • [9] Jakob F., DISSOLVED GAS ANAL P
  • [10] IMPROVED GAUGE CAPABILITY FOR ION IMPLANT MONITORS USING TEMPERATURE COMPENSATION FOR RESISTIVITY MEASUREMENTS
    JOHNSON, WH
    MALLORY, CL
    KEENAN, WA
    YETTER, G
    KAMENITSA, D
    [J]. NUCLEAR INSTRUMENTS & METHODS IN PHYSICS RESEARCH SECTION B-BEAM INTERACTIONS WITH MATERIALS AND ATOMS, 1993, 74 (1-2) : 229 - 233