Load Flow Calculation with Voltage Regulators Bidirectional Mode and Distributed Generation

被引:16
作者
Massignan, Julio A. D. [1 ]
Pereira, Benvindo R., Jr. [1 ]
London, Joao B. A., Jr. [1 ]
机构
[1] Univ Sao Paulo, BR-13566590 Sao Carlos, SP, Brazil
基金
巴西圣保罗研究基金会;
关键词
Distributed generation; distribution system; load flow analysis; voltage regulators; voltage control;
D O I
10.1109/TPWRS.2016.2576679
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This letter presents a problem of calculating load flow in distribution feeders via the conventional three-phase backward/forward sweep method when voltage regulators in the bidirectional mode are experiencing reverse flow due to power injection from distributed generation downstream the regulators. It also presents a simple but effectively modification in the algorithm of that method to overcome the problem. A modified version of the IEEE 34 buses distribution test feeder will be used to demonstrate the problem and the proposed algorithm solution.
引用
收藏
页码:1576 / 1577
页数:2
相关论文
共 4 条
[1]   Distribution Voltage Control Considering the Impact of PV Generation on Tap Changers and Autonomous Regulators [J].
Agalgaonkar, Yashodhan P. ;
Pal, Bikash C. ;
Jabr, Rabih A. .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2014, 29 (01) :182-192
[2]  
[Anonymous], MJ 4A TM MJ 4B TM VO
[3]  
CHENG CS, 1995, IEEE T POWER SYST, V10, P671, DOI 10.1109/59.387902
[4]   A Sensitivity Approach to Model Local Voltage Controllers in Distribution Networks [J].
Dzafic, Izudin ;
Jabr, Rabih A. ;
Halilovic, Ema ;
Pal, Bikash C. .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2014, 29 (03) :1419-1428