A live-line measurement method to parameters of high voltage cable lines with mutual inductance based on GPS

被引:0
作者
Hu, ZJ [1 ]
Zhang, CX [1 ]
Chen, YP [1 ]
机构
[1] Wuhan Univ, Sch Elect Engn, Wuhan 430072, Hubei, Peoples R China
来源
POWERCON 2002: INTERNATIONAL CONFERENCE ON POWER SYSTEM TECHNOLOGY, VOLS 1-4, PROCEEDINGS | 2002年
关键词
high voltage cable lines; zero-sequence; self-inductance; mutual inductance; live line measurement; GPS;
D O I
暂无
中图分类号
TP18 [人工智能理论];
学科分类号
081104 ; 0812 ; 0835 ; 1405 ;
摘要
The theoretical calculation method with formulae and the conventional measurement method of zero-sequence self-and mutual-impedance of high voltage cable lines are reviewed. Then the principles and mathematical models of zero-sequence parameter live-line measurement method of cable lines with mutual inductance based on GPS (Global Positioning System) technology are presented together with key,techniques, hardware structure and software algorithm of the measurement system. Finally, field measurement results with the three different methods are given. Theoretical analysis and field measurement results prove that this new live-line method proposed in the paper is correct, effective and efficient.
引用
收藏
页码:969 / 973
页数:5
相关论文
共 3 条
[1]  
CHEN YP, 1997, INT POW ENG C SING, P611
[2]  
CHEN YP, 1995, AUTOMATION ELECT POW, P18
[3]  
HE YZ, 1992, ELECT POWER SYSTEM A, P123