Vision-based thermal comfort quantification for HVAC control

被引:36
作者
Jung, Wooyoung [1 ]
Jazizadeh, Farrokh [2 ]
机构
[1] Virginia Tech, Via Dept Civil & Environm Engn, 315B Patton Hall,750 Drillfield Dr, Blacksburg, VA 24061 USA
[2] Virginia Tech, Via Dept Civil & Environm Engn, 200 Patton Hall,750 Drillfield Dr, Blacksburg, VA 24061 USA
基金
美国国家科学基金会;
关键词
User-centered HVAC system; Personalized thermal comfort; Photoplethysmography (PPG); Thermoregulation; Adaptive filtering; Skin temperature; Independent component analysis; INDEPENDENT COMPONENT ANALYSIS; SKIN TEMPERATURES; NONCONTACT; SENSATION; RESPONSES; PEOPLE; MOTION; LIGHT;
D O I
10.1016/j.buildenv.2018.05.018
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
This study presents a vision-based approach that employs RGB video images as the sole source for inferring thermoregulation states in the human body in response to thermal condition variations in indoor environments. The primary objective is to contribute to our envisioned thermoregulation-based HVAC control that leverages actual thermal demands from end-users' thermoregulation states for increased energy efficiency. Given that the envisioned control system calls for measurement techniques under four constraints of non-intrusiveness, applicability, sensitivity, and ubiquity (i.e., feasibility and scalability), this study investigated the potentials of ubiquitously obtainable RGB video images (through webcams or smartphones). Using photoplethysmography (PPG), a well-known optical technique for measuring blood volume changes in the microvascular bed of skin, we have leveraged the mechanism of blood flow control to the skin surface (blood vessels' dilation and constriction) for heat dissipation regulations, reflected in PPG signal's amplitude. Given the subtle variations of PPG signals and their susceptibility to noise, we proposed a framework that uses a combination of independent component analysis and adaptive filtering to reduce unwanted and in-band artifacts while preserving the amplitude information of PPG signals that indicates thermophysiological states. The framework was experimentally evaluated using transient thermal conditions to account for applicability and sensitivity attributes. Therefore, without considering an acclimation time for stabilized thermoregulation states, human subjects were exposed to varying temperatures (similar to 20-30 degrees C) while reporting their thermal sensations. In total, for 10 human subjects out of 15, a positive correlation between vision-based indicators, skin temperature, and thermal sensations were observed demonstrating promising potential in inferring thermal sensations of occupants with sufficient sensitivity.
引用
收藏
页码:513 / 523
页数:11
相关论文
共 67 条
[1]   Microvascular blood flow and skin temperature changes in the fingers following a deep inspiratory gasp [J].
Allen, J ;
Frame, JR ;
Murray, A .
PHYSIOLOGICAL MEASUREMENT, 2002, 23 (02) :365-373
[2]  
Allen J., 2007, PHYSIOL MEAS, P28
[3]  
[Anonymous], 2001, COMPUTER VISION PATT
[4]  
[Anonymous], 2007, Biofeedback
[5]  
[Anonymous], 2013, ASHRAE HDB FUND
[6]  
Apple Your Heart Rate, 2017, HEART RAT WHAT IT ME
[7]  
ASHRAE, 2017, THERM ENV COND HUM O
[8]   Thermal comfort in residential buildings - Failure to predict by Standard model [J].
Becker, R. ;
Paciuk, M. .
BUILDING AND ENVIRONMENT, 2009, 44 (05) :948-960
[9]   Investigation of human body skin temperatures as a bio-signal to indicate overall thermal sensations [J].
Choi, Joon-Ho ;
Loftness, Vivian .
BUILDING AND ENVIRONMENT, 2012, 58 :258-269
[10]   Thermal sensation of Hong Kong people with increased air speed, temperature and humidity in air-conditioned environment [J].
Chow, T. T. ;
Fong, K. F. ;
Givoni, B. ;
Lin, Zhang ;
Chan, A. L. S. .
BUILDING AND ENVIRONMENT, 2010, 45 (10) :2177-2183