A Novel Strategy for the Fault Detection and Diagnosis of Centrifugal Chiller Systems

被引:70
作者
Zhou, Qiang [1 ]
Wang, Shengwei [1 ]
Xiao, Fu [1 ]
机构
[1] Hong Kong Polytech Univ, Dept Bldg Serv Engn, Kowloon, Hong Kong, Peoples R China
来源
HVAC&R RESEARCH | 2009年 / 15卷 / 01期
关键词
BUILDING SYSTEMS; MODEL; PERFORMANCE; PROGNOSTICS;
D O I
10.1080/10789669.2009.10390825
中图分类号
O414.1 [热力学];
学科分类号
摘要
This paper presents a new fault detection and diagnosis (FDD) strategy for centrifugal chillers in building air-conditioning systems. The strategy is implemented using the fuzzy modeling and the artificial neural network techniques. Based on the sensitivity analysis of performance indices (PIs) to the chiller faults, the PI residuals between the model estimations using the normal data and the model estimations using the fault data are chosen to be normalized and to form a diagnostic classifier. The chosen PI risiduals are further quantified by the proposed fuzzy models. The fault identification is realized by neurasl network, using the quantitative diagnostic classifier. The use of the quantitative diagnostic classifier in this FDD strategy overcomes the problem faced by classical qualitative fault classifiers when different faults have the same linguistic rule pattern. The strategy implementation is based on the data at normal and faulty operating conditions at a range of load levels and fault severity levels. The strategy is validated using the laboratory chiller data provided by ASHRAE Research Project RP-1043 (Comstock and Braun 1999c).
引用
收藏
页码:57 / 75
页数:19
相关论文
共 23 条
  • [1] [Anonymous], P IEEE INT C NEUR NE
  • [2] Bailey M.B., 1998, THESIS U COLORADO BO
  • [3] The sensitivity of chiller performance to common faults
    Comstock, MC
    Braun, JE
    Groll, EA
    [J]. HVAC&R RESEARCH, 2001, 7 (03): : 263 - 279
  • [4] COMSTOCK MC, 1999, 40362 PURD U RAY HER
  • [5] COMSTOCK MC, 1999, 40363 PURD U HERR LA
  • [6] COMSTOCK MC, 1999, 40361 PURD U HERR LA
  • [7] A model-based online fault detection and diagnosis strategy for centrifugal chiller systems
    Cui, JT
    Wang, SW
    [J]. INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2005, 44 (10) : 986 - 999
  • [8] Fault diagnosis in air-conditioning systems: A multi-step fuzzy model-based approach
    Dexter, AL
    Ngo, D
    [J]. HVAC&R RESEARCH, 2001, 7 (01): : 83 - 102
  • [9] PREDICTIVE AND DIAGNOSTIC ASPECTS OF A UNIVERSAL THERMODYNAMIC MODEL FOR CHILLERS
    GORDON, JM
    NG, KC
    [J]. INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 1995, 38 (05) : 807 - 818
  • [10] Characteristic physical parameter approach to modeling chillers suitable for fault detection, diagnosis, and evaluation
    Jia, YZ
    Reddy, TA
    [J]. JOURNAL OF SOLAR ENERGY ENGINEERING-TRANSACTIONS OF THE ASME, 2003, 125 (03): : 258 - 265