A Linear Estimator For Transmission Line Parameters Based On Distributed Parameter Line Model

被引:0
|
作者
Jiao, Xiangqing [1 ]
Liao, Yuan [1 ]
机构
[1] Univ Kentucky, Dept Elect & Comp Engn, Lexington, KY 40506 USA
关键词
bad measurement detection and identification; distributed parameter line model; linear estimation; transmission line parameter estimation; LOCATION; FAULT;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Transmission line parameters are critical inputs to a variety of power system analysis algorithms. To ensure the precision of line parameters, this paper proposes a novel linear method to estimate transmission line parameters, including series resistance, series reactance, and shunt susceptance, for non-compensated and series-compensated lines. Voltage and current phasors obtained by phasor measurement units (PMUs) from both ends are utilized in the algorithm. Linear least squares method is applied when multiple sets of measurements are available for improved accuracy. Distributed parameter line model is employed in developing the algorithm. An optimal estimator is also proposed, which can detect and identify possible measurement errors, although this type of method is no longer linear. The estimated line parameters can be used to determine line temperature and conductor sag. Evaluations studies demonstrate the effectiveness of the proposed methods.
引用
收藏
页数:8
相关论文
共 50 条
  • [1] Phase distance protection of transmission line based on distributed parameter model
    Ma, J. (hdmajing@yahoo.com.cn), 1600, Electric Power Automation Equipment Press (32):
  • [2] Distance protection for HVDC transmission line based on distributed parameter model
    Suonan, Jiale
    Hou, Zhuo
    Song, Guobing
    Zhang, Jiankang
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2011, 35 (08): : 53 - 57
  • [3] A fault location method for DC transmission line based on the distributed parameter model considering line parameter uncertainty
    Xia, Chengjun
    Yang, Mingjia
    Chi, Zibin
    ELECTRIC POWER SYSTEMS RESEARCH, 2025, 238
  • [4] Parameter Identification Algorithm for Fault Location Based on Distributed Transmission Line model
    Kang, Xiaoning
    Jiale, Suonan
    Bo, Zhiqian
    Tang, Jian
    Jun, Qi
    2008 IEEE POWER & ENERGY SOCIETY GENERAL MEETING, VOLS 1-11, 2008, : 4098 - +
  • [5] Fault-Location Algorithms Without Utilizing Line Parameters Based on the Distributed Parameter Line Model
    Liao, Yuan
    Kang, Ning
    IEEE TRANSACTIONS ON POWER DELIVERY, 2009, 24 (02) : 579 - 584
  • [6] Fault location using the distributed parameter transmission line model
    Gopalakrishnan, A
    Kezunovic, M
    McKenna, SM
    Hamai, DM
    IEEE TRANSACTIONS ON POWER DELIVERY, 2000, 15 (04) : 1169 - 1174
  • [7] Compacting distributed parameter transmission line model in EMTP-programs
    Paz, MA
    Tavares, MC
    Pissolato, J
    Portela, CM
    2004 IEEE/PES TRANSMISSION & DISTRIBUTION CONFERENCE & EXPOSITION: LATIN AMERICA, 2004, : 196 - 200
  • [8] Transmission line pilot protection based on frequency-domain model identification of distributed parameter
    Suonan, J. (suonan@263.net), 1600, Chinese Society for Electrical Engineering (33):
  • [9] Modal current differential protection method based on distributed parameter model of an HVDC transmission line
    Shao, Qingzhu
    Zhao, Xiaodong
    Zhao, Chuangye
    Ping, Xia
    Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control, 2021, 49 (22): : 171 - 179
  • [10] Hybrid Measurement-Based Parameter Estimator for Series Transmission Line and Power Transformer
    Mousavi-Seyedi, Seyed Sina