Development of ejector performance map for predicting fixed-geometry two-phase ejector performance for wide range of operating conditions

被引:11
作者
Haider, Muhammad [1 ]
Elbel, Stefan [1 ]
机构
[1] Univ Illinois, Dept Mech Sci & Engn, Air Conditioning & Refrigerat Ctr, 1206 West Green St, Urbana, IL 61801 USA
关键词
Two-phase ejector; Ejector performance map; Ejector performance prediction; Ejector efficiency; Ejector system analysis; WORK RECOVERY; REFRIGERATION; DESIGN;
D O I
10.1016/j.ijrefrig.2021.03.022
中图分类号
O414.1 [热力学];
学科分类号
摘要
Recent studies have expanded the operational envelope of ejector by utilizing both pressure recovery and liquid recirculation mechanisms. This necessitates finding a consistent representation of fixed-geometry ejector performance data using only operational variables for predicting ejector performance. Taking inspiration from the compressor performance maps, the study explores the appropriate motive, performance, and characterization variable for representing ejector performance while conducting experiments on a transcritical CO2 ejector system. The existing ejector efficiency is revisited by conducting ejector power analysis. Two possible motive variables, along with a new ejector efficiency is introduced. The trends of existing and new ejector efficiencies are studied in controlled motive variable experiments while changing suction flow conditions. The ejector performance can be represented with the help of a single curve, termed as ejector performance map, using the new ejector efficiency as performance variable and the volumetric entrainment ratio as characterization variable. The prediction accuracy for both the single-phase and the two-phase suction inlet conditions are evaluated while developing performance map using only the single-phase suction inlet data points. The methodology can predict 89.3% of the data within 20% accuracy. The applicability of the methodology is assessed for other datasets involving different refrigerants, cycle architectures, and applications. The proposed ejector performance map can be utilized in numerical ejector system analysis for investigating new cycle architectures based on ejector experimental data, thus, improving system model fidelity. It can also help system design engineers in making ejector system selection decisions after thorough system performance analysis. (C) 2021 Elsevier Ltd and IIR. All rights reserved.
引用
收藏
页码:232 / 241
页数:10
相关论文
共 16 条
[1]   Current Advances in Ejector Modeling, Experimentation and Applications for Refrigeration and Heat Pumps. Part 2: Two-Phase Ejectors [J].
Aidoun, Zine ;
Ameur, Khaled ;
Falsafioon, Mehdi ;
Badache, Messaoud .
INVENTIONS, 2019, 4 (01)
[2]   Development and performance mapping of a multi-ejector expansion work recovery pack for R744 vapour compression units [J].
Banasiak, Krzysztof ;
Hafner, Armin ;
Kriezi, Ekaterini E. ;
Madsen, Kenneth B. ;
Birkelund, Michael ;
Fredslund, Kristian ;
Olsson, Rickard .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2015, 57 :265-276
[3]  
Barta R.B., 2021, APPL THERM ENG
[4]   Experimental validation of a prototype ejector designed to reduce throttling losses encountered in transcritical R744 system operation [J].
Elbel, Stefan ;
Hrnjak, Pega .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2008, 31 (03) :411-422
[5]   Experimental and computational analysis of a R744 flashing ejector [J].
Giacomelli, Francesco ;
Mazzelli, Federico ;
Banasiak, Krzysztof ;
Hafner, Armin ;
Milazzo, Adriano .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2019, 107 :326-343
[6]  
Haider M., 2020, SAE WORLD C DETR MI
[7]   Experimental investigation on control methods and strategies for off-design operation of the transcritical R744 two-phase ejector cycle [J].
Lawrence, Neal ;
Elbel, Stefan .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2019, 106 :570-582
[8]   Experimental investigation on the effect of evaporator design and application of work recovery on the performance of two-phase ejector liquid recirculation cycles with R410A [J].
Lawrence, Neal ;
Elbel, Stefan .
APPLIED THERMAL ENGINEERING, 2016, 100 :398-411
[9]   Experimental investigation of a two-phase ejector cycle suitable for use with low-pressure refrigerants R134a and R1234yf [J].
Lawrence, Neal ;
Elbel, Stefan .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2014, 38 :310-322
[10]   Study of ejector efficiencies in refrigeration cycles [J].
Liu, Fang ;
Groll, Eckhard A. .
APPLIED THERMAL ENGINEERING, 2013, 52 (02) :360-370