A Novel Power Transformer Condition Monitoring System Based on Wide-Band Measurement of Core Earth Signals and Correlation Analysis With Multi-Source Data

被引:6
作者
Ke, Xuezhi [1 ]
Pang, Lisheng [2 ]
Dong, Xiang [3 ]
Li, Zhaohui [4 ]
机构
[1] Huazhong Univ Sci & Technol, Sch Hydropower & Informat Engn, Wuhan 430074, Hubei, Peoples R China
[2] Datang Guanyinyan Hydroelect Dev Co, Panzhihua 617000, Peoples R China
[3] Beijing Maintenance Co, China State Grid, Beijing 100000, Peoples R China
[4] Huazhong Univ Sci & Technol, State Key Lab Adv Electromagnet Engn & Technol, Wuhan 430074, Hubei, Peoples R China
关键词
Feature extraction; Power transformers; Transformer cores; Correlation; Partial discharges; Condition monitoring; Monitoring; Correlation analysis; core earth signal (CES); condition monitoring; industry applications; power transformer; wide-band measurement;
D O I
10.1109/ACCESS.2019.2951577
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
On-line condition monitoring and real-time fault detection are essential to protect power transformers from unscheduled outage of services. The core earth signals (CES) are valuable for fault detection and diagnosis of power transformers, as they are related to multiple transformer defects and faults, such as core multi-point earthing fault and core deep saturation. Moreover, the CES also contain valuable information of transient impulses intruded into power transformers such as very fast transient overvoltage (VFTO) impulses. This paper develops a novel power transformer condition monitoring system (NCMS), which makes full use of CES to detect and diagnose the external impulses and internal defects and faults. Firstly, the NCMS carries out the wide-band measurement of CES. Secondly, the NCMS obtains data from supervisory control and data acquisition system (SCADAS), dissolved gases analysis (DGA) system, and other monitoring systems, and correlates these data using grey relational analysis (GRA). Finally, the NCMS detects the impulses and diagnoses defects and faults based on the correlation relationships, then presents the monitoring results to the users. This novel system has been applied to the field and successfully diagnosed many defects and faults. It has high accuracy ( 3) at the power and harmonic frequencies and possesses the capability to capture VFTO-pulses.
引用
收藏
页码:161754 / 161763
页数:10
相关论文
共 29 条
[1]  
[Anonymous], C5712902010 IEEE
[2]  
[Anonymous], 2003, 227 CIGRE
[3]  
[Anonymous], 2002, ELEMENTS GREY THEORY
[4]  
[Anonymous], 2001, 60270 2000 IEC BSI, P53
[5]   Fuzzy Logic Approach in Power Transformers Management and Decision Making [J].
Arshad, Muhammad ;
Islam, Syed M. ;
Khaliq, A. .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2014, 21 (05) :2343-2354
[6]   Partial Discharge Recognition Based on Optical Fiber Distributed Acoustic Sensing and a Convolutional Neural Network [J].
Che, Qian ;
Wen, Hongqiao ;
Li, Xinyu ;
Peng, Zhaoqiang ;
Chen, Keven P. .
IEEE ACCESS, 2019, 7 :101758-101764
[7]   Study of on-line monitoring method of partial discharge for power transformers based on RFCT and microstrip antenna [J].
Cheng, YH ;
Chen, Y ;
Liu, T ;
Xu, XW ;
Ji, LL ;
Chen, W ;
Chen, LX .
PROCEEDINGS: ELECTRICAL INSULATION CONFERENCE AND ELECTRICAL MANUFACTURING CONFERENCE, 2005, :103-107
[8]  
Costa F., 2001, EPE Journal, V11, P7
[9]  
Feng W, 2014, IEEE INT POWER MODUL, P241, DOI 10.1109/IPMHVC.2014.7287253
[10]   PD-source localization in the insulating system of large power transformers [J].
Fuhr, Jitka .
Conference Record of the 2006 IEEE International Symposium on Electrical Insulation, 2006, :424-427