Design and evaluation of a circulating current differential relay test system

被引:14
作者
Crossley, PA [1 ]
Li, HY
Parker, AD
机构
[1] UMIST, Manchester Ctr Elect Energy, Manchester M60 1QD, Lancs, England
[2] GEC ALSTHOM T&D, Stafford, England
关键词
circulating current differential protection; current transformer behaviour; digital modelling of current transformers; differential protection test system; synthetic test plant;
D O I
10.1109/61.660910
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper describes how an EMTP based simulator can be used in conjunction with a relay test set to type-test a protection relay operating within a circulating current differential protection scheme. The combination of a simulator and a test-set is designed to replace a high power synthetic test plant that has been used for more than 30 years for type and approval testing of differential protection relays. The paper will include results that describe the operating performance of the new test system, on both internal and external faults, and these will be compared with experimental results obtained fi om an identical set of tests on the synthetic test plant.