Highly Reliable Operation Control for MMC-UPFC under Unbalanced Power Grid Conditions

被引:1
作者
Hu, Jijun [1 ]
Zhu, Dongsheng [1 ]
Xiong, Jing [1 ]
Zhu, Haifeng [2 ]
Bo, Bin [2 ]
Liu, Xiaofan [2 ]
Wei, Xiaojing [3 ]
机构
[1] Jiangsu Power Design Inst Co, China Energy Engn Grp, Nanjing, Jiangsu, Peoples R China
[2] State Grid Jiangsu Elect Power Co, Nanjing, Jiangsu, Peoples R China
[3] Southeast Univ, Elect Engn Coll, Nanjing, Jiangsu, Peoples R China
来源
2018 IEEE INTERNATIONAL CONFERENCE ON INDUSTRIAL TECHNOLOGY (ICIT) | 2018年
关键词
MMC-UPFC; unbalanced condition; negative sequence compensation; decoupling control; CONVERTER; HVDC;
D O I
10.1109/ICIT.2018.8352269
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
The grid contains many negative sequence components under unbalanced conditions, which affect the safe operation of MMC-UPFC. To achieve highly reliable operation control for MMC-UPFC under unbalanced conditions, this paper proposes a decoupling control strategy that introduces the separation of positive and negative sequences. First, the working principles and mathematical model of MMC-UPFC are analyzed. Second, the instantaneous symmetric component method is introduced to separate the positive and negative sequence components of the grid. After that step, dq decoupling control strategies under positive and negative sequences are designed for the shunt side and series side, respectively, which can realize negative sequence compensation and highly reliable operation of MMC-UPFC. Simulation results are presented to verify the effectiveness and feasibility of the proposed control strategy.
引用
收藏
页码:736 / 741
页数:6
相关论文
共 11 条
[1]   Mitigation of unbalanced voltage dips using static series compensator [J].
Awad, H ;
Svensson, J ;
Bollen, M .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2004, 19 (03) :837-846
[2]   Effect of sampling frequency and harmonics on delay-based phase-sequence estimation method [J].
Bongiorno, Massimo ;
Svensson, Jan ;
Sannino, Ambra .
IEEE TRANSACTIONS ON POWER DELIVERY, 2008, 23 (03) :1664-1672
[3]   A Novel SPLL and Voltage Sag Detection Based on LES Filters and Improved Instantaneous Symmetrical Components Method [J].
Chen, Guodong ;
Zhang, Liang ;
Wang, Ruiting ;
Zhang, Luhua ;
Cai, Xu .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2015, 30 (03) :1177-1188
[4]   Control and Analysis of the Modular Multilevel Cascade Converter Based on Double-Star Chopper-Cells (MMCC-DSCC) [J].
Hagiwara, Makoto ;
Maeda, Ryo ;
Akagi, Hirofumi .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2011, 26 (06) :1649-1658
[5]   Software Sensor-Based STATCOM Control Under Unbalanced Conditions [J].
Leon, Andres E. ;
Manuel Mauricio, Juan ;
Solsona, Jorge A. ;
Gomez-Exposito, Antonio .
IEEE TRANSACTIONS ON POWER DELIVERY, 2009, 24 (03) :1623-1632
[6]  
Liu Y, 2011, INT C COMP AID IND D, P378
[7]   UPFC for Enhancing Power System Reliability [J].
Rajabi-Ghahnavieh, A. ;
Fotuhi-Firuzabad, M. ;
Shahidehpour, M. ;
Feuillet, R. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2010, 25 (04) :2881-2890
[8]   Dynamic Performance of a Modular Multilevel Back-to-Back HVDC System [J].
Saeedifard, Maryam ;
Iravani, Reza .
IEEE TRANSACTIONS ON POWER DELIVERY, 2010, 25 (04) :2903-2912
[9]   Modeling of UPFC operation under unbalanced conditions with dynamic phasors [J].
Stefanov, PC ;
Stankovic, AM .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2002, 17 (02) :395-403
[10]   Suppressing DC Voltage Ripples of MMC-HVDC Under Unbalanced Grid Conditions [J].
Tu, Qingrui ;
Xu, Zheng ;
Chang, Yong ;
Guan, Li .
IEEE TRANSACTIONS ON POWER DELIVERY, 2012, 27 (03) :1332-1338