Comparison of the effectiveness of thriple-loop and double-loop systems of active shielding of a magnetic field in a multi-storey old buildings

被引:2
作者
Kuznetsov, B., I [1 ]
Nikitina, T. B. [2 ]
Bovdui, I., V [1 ]
Voloshko, O. V. [1 ]
Kolomiets, V. V. [2 ]
Kobylianskyi, B. B. [2 ]
机构
[1] Natl Acad Sci Ukraine, A Pidhornyi Inst Mech Engn Problems, 2-10 Pozharskogo Str, UA-61046 Kharkiv, Ukraine
[2] Ukrainian Engn Pedag Acad, Educ Sci Profess Pedag Inst, 9a Nosakov Str, UA-84511 Bakhmut, Donetsk Region, Ukraine
关键词
overhead power line; magnetic field; system of active screening; computer simulation; experimental research; ALGORITHMS; SIMULATION; REDUCTION; DESIGN;
D O I
10.20998/2074-272X.2022.3.04
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Aim. The issues of comparing the effectiveness of reducing the level of the magnetic field in afive-storey old buildings generated by a single-circuit overhead power transmission lines with a triangular suspension of wires using a thriple-loop and double-loop systems of active screening, which respectively contain three or two compensating windings are considered. Methodology Spatial location coordinates of the compensating windings and the currents in the shielding windings were determined during the design of systems of active screening based on solution of the maximin vector optimization problem, in whith the vector of objective function is calculated based on Biot-Savart's law. The solution of this problem is calculated based on algorithms of multi-swarm multi-agent optimization. Results. The results of theoretical and experimental comparing the effectiveness of reducing the level of the magnetic field in a five-storey old generated by a single-circuit overhead power transmission lines with a triangular suspension of wires using a thriple-loop and double-loop systems of active screening, which respectively contain three or two compensating windings are presented. Originality For the first time, the comparison the effectiveness of reducing the level of the magnetic field in a five-storey old using a thriple-loop and double-loop systems of active screening are considered. Practical value. From the point of view of the practical implementation it is shown the possibility to reduce the level of magnetic field induction in a five-storey old buildings to the sanitary standards of Ukraine for real overhead power transmission lines currents with the help of a synthesized double-loop systems of active screening. A double-loop active screening system is simpler in comparison with a thriple-loop active screening system when implementing.
引用
收藏
页码:21 / 27
页数:7
相关论文
共 48 条
[1]  
[Anonymous], 2009, MULTIAGENT SYSTEMS A
[2]  
Averyanova Yuliya, 2021, Data Science and Security: Proceedings of IDSCS 2021. Lecture Notes in Networks and Systems (290), P258, DOI 10.1007/978-981-16-4486-3_28
[3]   Active shielding of overhead line magnetic field: Design and applications [J].
Barsali, Stefano ;
Giglioli, Romano ;
Poli, Davide .
ELECTRIC POWER SYSTEMS RESEARCH, 2014, 110 :55-63
[4]   Magnetic Field Mitigation at Power Frequency: Design Principles and Case Studies [J].
Bavastro, Davide ;
Canova, Aldo ;
Freschi, Fabio ;
Giaccone, Luca ;
Manca, Michele .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2015, 51 (03) :2009-2016
[5]  
Beltran H., 2005, 9 C HISP LUS ING EL, P84
[6]   MATHEMATICAL MODELLING OF TRANSIENTS IN THE ELECTRIC DRIVE OF THE SWITCH - THE MAIN EXECUTIVE ELEMENT OF RAILWAY AUTOMATION [J].
Buriakovskyi, S. G. ;
Maslii, A. S. ;
Pasko, O., V ;
Smirnov, V. V. .
ELECTRICAL ENGINEERING & ELECTROMECHANICS, 2020, (04) :17-23
[7]  
Canova Aldo, 2017, CIRED - Open Access Proceedings Journal, V2017, P686, DOI 10.1049/oap-cired.2017.1029
[8]  
Canova A., 2019, PROC 25 INT C ELECTR
[9]   Real-time optimization of active loops for the magnetic field minimization [J].
Canova, Aldo ;
Giaccone, Luca .
INTERNATIONAL JOURNAL OF APPLIED ELECTROMAGNETICS AND MECHANICS, 2018, 56 :S97-S106
[10]   Active Shielding System for ELF Magnetic Fields [J].
Canova, Aldo ;
Carlos del-Pino-Lopez, Juan ;
Giaccone, Luca ;
Manca, Michele .
IEEE TRANSACTIONS ON MAGNETICS, 2015, 51 (03)