Smart grids cyber-physical security as a malicious data attack: An innovation approach

被引:47
作者
Bretas, Arturo S. [1 ]
Bretas, Newton G. [2 ]
Carvalho, Breno [1 ]
Baeyens, Enrique [3 ]
Khargonekar, Pramod P. [4 ]
机构
[1] Univ Florida, Dept Elect & Comp Engn, Gainesville, FL 32611 USA
[2] Univ Sao Paulo, Dept Elect & Comp Engn, BR-13566590 Sao Carlos, SP, Brazil
[3] Univ Valladolid, Dept Syst Engn & Automat, E-47002 Valladolid, Spain
[4] Univ Calif Irvine, Irvine, CA 92697 USA
基金
美国国家科学基金会; 巴西圣保罗研究基金会;
关键词
Smart grids; Cyber-physical systems security; State estimation; Innovation concept; Bad data analysis; GROSS ERROR-DETECTION; STATE ESTIMATION; IDENTIFICATION;
D O I
10.1016/j.epsr.2017.04.018
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents an analytical methodology for smart grids cyber-physical security based on gross error analysis. The presented methodology is built on the Weighted Least Square (WLS) state estimator (SE) formulation. Although cyber-physical security is a wide subject, in this paper Cyber-Attacks are modeled as bad data. Detection, identification and correction of multiple and simultaneous cyber-attacks on power grid's SCADA system, or network database, are investigated. Cyber-attack detection is made through a Chi-square (x(2)) Hypothesis Testing (HT) applied to the composed measurement error (CME). Composed errors are estimated with measurements' innovation index (II). Cyber-attack identification is made through the Largest Normalized Error Test property. Cyber-attack correction is made considering cyber-attack type and using the composed normalized error (CNE). One important advantage of the presented method is it does not require a previous knowledge of how the attack was performed, as far as it is restricted to a change of measurements, parameters or topology, since the error is estimated and then the bad data is corrected. A significant advantage of this correction is that it avoids potential local or global unobservable conditions, since it does not delete any measurement of the measurement set. Validation of the proposed methodology is made on the IEEE 14-bus and 57-bus systems. Simulations show the reliability and robustness of the proposed methodology even when the cyber-attack occurs simultaneously on SCADA data and network database. Published by Elsevier B.V.
引用
收藏
页码:210 / 219
页数:10
相关论文
共 24 条
[1]  
[Anonymous], STATE ESTIMATION ELE
[2]  
[Anonymous], P 16 ACM C COMP COMM
[3]  
[Anonymous], 2016, Forbes
[4]  
Ashok A., 2016, IEEE T SMART GRID, P1
[5]   Innovation concept for measurement gross error detection and identification in power system state estimation [J].
Bretas, N. G. ;
Bretas, A. S. ;
Piereti, S. A. .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2011, 5 (06) :603-608
[6]   A two steps procedure in state estimation gross error detection, identification, and correction [J].
Bretas, Newton G. ;
Bretas, Arturo S. .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2015, 73 :484-490
[7]   A Geometrical View for Multiple Gross Errors Detection, Identification, and Correction in Power System State Estimation [J].
Bretas, Newton G. ;
Piereti, Saulo A. ;
Bretas, Arturo S. ;
Martins, Andre C. P. .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2013, 28 (03) :2128-2135
[8]  
Chakhchoukh Y., 2016, IEEE T POWER SYST, P1
[9]   Coordinated Cyber-Attacks on the Measurement Function in Hybrid State Estimation [J].
Chakhchoukh, Yacine ;
Ishii, Hideaki .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2015, 30 (05) :2487-2497
[10]  
Christie R.D., 1999, Power Systems Test Case Archive