Modelling and evaluation of cooling capacity of earth-air-pipe systems

被引:123
作者
Wu, Huijun
Wang, Shengwei [1 ]
Zhu, Dongsheng
机构
[1] Hong Kong Polytech Univ, Dept Bldg Serv Engn, Hong Kong, Hong Kong, Peoples R China
[2] S China Univ Technol, Sch Chem & Energy Engn, Key Lab Enhanced Heat Transfer & Energy Conservat, Minist Educ, Guangzhou 510640, Peoples R China
关键词
earth-air-pipe; thermal performance; cooling capacity; soil temperature; space cooling; energy conservation;
D O I
10.1016/j.enconman.2006.12.021
中图分类号
O414.1 [热力学];
学科分类号
摘要
Earth-air-pipe systems can be used to reduce the cooling load of buildings in summer. A transient and implicit model based on numerical heat transfer and computational fluid dynamics was developed to predict the thermal performance and cooling capacity of earth-air-pipe systems. Superposition technology is used in the model, incorporating the natural ground temperature field and the turbulent air flow inside the buried pipe. The model developed is validated against experimental investigations on an experimental set-up in Southern China. Good agreement between simulated results and experimental data is obtained. The model is then implemented on the CFD (Computational Fluid Dynamics platform), PHOENICS, to evaluate the effects of the operating parameters (i.e. the pipe length, radius, depth and air flow rate) on the thermal performance and cooling capacity of earth-air-pipe systems. A daily cooling capacity up to 74.6 kW h can be obtained from an earth-air-pipe system installed in that region. (C) 2007 Elsevier Ltd. All rights reserved.
引用
收藏
页码:1462 / 1471
页数:10
相关论文
共 29 条
[1]   The cooling potential of earth-air heat exchangers for domestic buildings in a desert climate [J].
Al-Ajmi, F ;
Loveday, DL ;
Hanby, VI .
BUILDING AND ENVIRONMENT, 2006, 41 (03) :235-244
[2]   Ground heat exchanger temperature distribution analysis and experimental verification [J].
Bi, YH ;
Chen, LG ;
Wu, C .
APPLIED THERMAL ENGINEERING, 2002, 22 (02) :183-189
[3]   Energy from a two-pipe, earth-to-air heat exchanger [J].
Bojic, M ;
Papadakis, G ;
Kyritsis, S .
ENERGY, 1999, 24 (06) :519-523
[4]  
Carslaw H.S., 1980, Conduction of Heat in Solids
[5]   Experimental study of a closed loop vertical ground source heat pump system [J].
Hepbasli, A ;
Akdemir, O ;
Hancioglu, E .
ENERGY CONVERSION AND MANAGEMENT, 2003, 44 (04) :527-548
[6]   Energy and exergy analysis of a ground source (geothermal) heat pump system [J].
Hepbasli, A ;
Akdemir, O .
ENERGY CONVERSION AND MANAGEMENT, 2004, 45 (05) :737-753
[7]  
HOKOI S, 1998, ASHRAE T, V104, P398
[8]  
Jacovides C. P., 1996, SOL ENERGY, V57, P467
[9]   An underground pipe system as an energy source for cooling heating purposes [J].
Jacovides, CP ;
Mihalakakou, G .
RENEWABLE ENERGY, 1995, 6 (08) :893-900
[10]  
JURGES W, 1924, BEIH Z, V19, P51