Application of Voltage Response Measurement on Low Voltage Cables

被引:13
作者
Tamus, Z. A. [1 ]
Berta, I. [1 ]
机构
[1] Budapest Univ Technol & Econ, H-1111 Budapest, Hungary
来源
2009 IEEE ELECTRICAL INSULATION CONFERENCE | 2009年
关键词
INSULATION;
D O I
10.1109/EIC.2009.5166387
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The application of voltage response measurement is a very effective tool to determine of the aging state of oil-paper insulated cables. The initial slope of the decay voltage is directly proportional to the conductivity of the insulation and the initial slope of the return voltage is proportional to the intensity of polarization processes. Therefore, the two main deterioration processes (moistening and thermal aging) of oil-paper insulation can be examined independently. In this paper, the application of voltage response method is examined on laboratory aged low voltage polymeric (PVC and PE) insulated cables and the results were compared to the results of chemical and breakdown tests. By the using of voltage response method the aging state of the insulation i.e. the probable decrease of dielectric strength can be detected.
引用
收藏
页码:444 / 447
页数:4
相关论文
共 10 条
[1]   Nuclear qualification of PVC insulated cables [J].
Anandakumaran, K ;
Barreca, S ;
Seidl, W ;
Castaldo, PV .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2001, 8 (05) :818-825
[2]   Condition assesment of cable insulation systems in operating nuclear power plants [J].
Anandakumaran, K ;
Seidl, W ;
Castaldo, PV .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 1999, 6 (03) :376-384
[3]   ac aging and space-charge characteristics in low-density polyethylene polymeric insulation [J].
Chen, G ;
Fu, M ;
Liu, XZ ;
Zhong, LS .
JOURNAL OF APPLIED PHYSICS, 2005, 97 (08)
[4]  
FU M, IEEE INT C SOL DIEL, P217
[5]   Measuring voltage response:: a non-destructive diagnostic test method of HV insulation [J].
Németh, E .
IEE PROCEEDINGS-SCIENCE MEASUREMENT AND TECHNOLOGY, 1999, 146 (05) :249-252
[6]  
Nemeth E., 1997, P 10 INT S HV ENG IS, V4, P191
[7]  
NEMETH E, 1994, P SER POW ENG HIGH V, V6, P34
[8]  
TAMUS ZA, IEEE EL I C IN PRESS
[9]   Effect of voltage stress on diagnostic parameters of low voltage cables [J].
Tamus, Zoltan Adam ;
Nemeth, Balint ;
Berta, Istvan .
CONFERENCE RECORD OF THE 2008 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION, VOLS 1 AND 2, 2008, :43-46
[10]   Complex diagnostics of insulating materials in industrial electrostatics [J].
Tamus, Zoltan Adam .
JOURNAL OF ELECTROSTATICS, 2009, 67 (2-3) :154-157