Analysis of Active Power Control for VSC-HVDC

被引:124
作者
Wang, Wenyuan [1 ]
Beddard, Antony [1 ]
Barnes, Mike [1 ]
Marjanovic, Ognjen [1 ]
机构
[1] Univ Manchester, Sch Elect & Elect Engn, Manchester M13 9PL, Lancs, England
基金
英国工程与自然科学研究理事会;
关键词
Active power control; droop control; modular multilevel converter (MMC); multiterminal dc (MTDC); voltage-source converter (VSC) HVDC; MMC;
D O I
10.1109/TPWRD.2014.2322498
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents a comprehensive analysis of the limitations and the key dynamics of closed-loop active power control systems for voltage-source converter (VSC) HVDC, regarding stability, performance, and robustness. Detailed dynamic models are derived and the controllability and robustness issues for VSC active power control are identified. Limitations imposed by ac system strength, converter operating point, and current control design on the stability and performance of the two leading active power control principles are addressed, using frequency-response analysis and time-domain simulations. The dynamic interactions between the active power control design and the dc voltage droop control are examined. The simulations are performed using average-value VSC models and a high-fidelity modular multilevel converter model. Impacts of the active power control design on dynamic behaviors of multiterminal dc (MTDC) systems are investigated using a four-terminal model. This paper provides a systematic study on the key stability and performance issues associated with the active power control. Furthermore, the methodology offers a framework for the analysis of more complex active power and dc voltage droop controllers for future MTDC systems.
引用
收藏
页码:1978 / 1988
页数:11
相关论文
共 23 条
[1]  
Alstom Grid, 2010, HVDC CONN FUT
[2]  
[Anonymous], 2011, 2011 IEEE POWER ENER
[3]  
[Anonymous], 2009, 13 EUR C POW EL APPL
[4]   Stability Analysis of VSC MTDC Grids Connected to Multimachine AC Systems [J].
Chaudhuri, Nilanjan Ray ;
Majumder, Rajat ;
Chaudhuri, Balarko ;
Pan, Jiuping .
IEEE TRANSACTIONS ON POWER DELIVERY, 2011, 26 (04) :2774-2784
[5]  
CIGRE Working Group B4-37, 2005, B437 CIGRE
[6]  
CIGRE Working Group C4/B4/C1.604, 2013, C4B4C1604 CIGRE
[7]   A distributed DC voltage control method for VSC MTDC systems [J].
Dierckxsens, C. ;
Srivastava, K. ;
Reza, M. ;
Cole, S. ;
Beerten, J. ;
Belmans, R. .
ELECTRIC POWER SYSTEMS RESEARCH, 2012, 82 (01) :54-58
[8]  
Durrant M, 2003, CCA 2003: PROCEEDINGS OF 2003 IEEE CONFERENCE ON CONTROL APPLICATIONS, VOLS 1 AND 2, P178
[9]   Efficient Modeling of Modular Multilevel HVDC Converters (MMC) on Electromagnetic Transient Simulation Programs [J].
Gnanarathna, Udana N. ;
Gole, Aniruddha M. ;
Jayasinghe, Rohitha P. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2011, 26 (01) :316-324
[10]   Impact of DC Line Voltage Drops on Power Flow of MTDC Using Droop Control [J].
Haileselassie, Temesgen M. ;
Uhlen, Kjetil .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2012, 27 (03) :1441-1449