Paralleled multi-terminal DC transmission line fault locating method based on travelling wave

被引:30
作者
Cheng, Jingzhou [1 ]
Guan, Minyuan [2 ]
Tang, Lv [3 ]
Huang, Hongyang [1 ]
Chen, Xin [3 ]
Xie, Jiajia [3 ]
机构
[1] Zhejiang Univ, Dept Elect Engn, Hangzhou 310027, Zhejiang, Peoples R China
[2] Zhejiang Elect Power Corp, Huzhou Power Supply Co, Huzhou 313000, Peoples R China
[3] Zhejiang Elect Power Corp, Hangzhou 310007, Zhejiang, Peoples R China
关键词
PROTECTION SCHEME; HVDC;
D O I
10.1049/iet-gtd.2013.0886
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This study presents a novel protection criterion of fault locating in multi-terminal DC (MTDC) transmission systems. When a fault occurs on the DC transmission line of the MTDC system, the traditional protection cannot locate the fault because there is no smoothing reactor (equipped at the converter output) in the transmission lines. In the circumstance of AC/DC conductor contact (ADCC) fault, the varieties of the transient voltage and current components are given based on the symmetrical fault analysis. According to the Bergeron equation, the travelling wave characteristic is analysed. A new criterion of fault locating using the change rate of the current travelling wave is presented which can reduce the impacts of the related fault on the AC system. Finally, simulation results verify the effectiveness of the proposed protection criterion.
引用
收藏
页码:2092 / 2101
页数:10
相关论文
共 28 条
[1]  
[Anonymous], 2011, IEEE POW EN SOC GEN
[2]  
[Anonymous], POWER SYSTEM STABILI
[3]  
[Anonymous], NEW TYPES PROTECTIVE
[4]  
[Anonymous], CIGRE SESS PAR FRANC
[5]   Generalized Dynamic VSC MTDC Model for Power System Stability Studies [J].
Cole, Stijn ;
Beerten, Jef ;
Belmans, Ronnie .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2010, 25 (03) :1655-1662
[6]   Coordinated primary frequency control among non-synchronous systems connected by a multi-terminal high-voltage direct current grid [J].
Dai, J. ;
Phulpin, Y. ;
Sarlette, A. ;
Ernst, D. .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2012, 6 (02) :99-108
[7]   Wavelet-based protection strategy for DC faults in multi-terminal VSC HVDC systems [J].
De Kerf, K. ;
Srivastava, K. ;
Reza, M. ;
Bekaert, D. ;
Cole, S. ;
Van Hertem, D. ;
Belmans, R. .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2011, 5 (04) :496-503
[8]   THE APPLICATION OF SATELLITE TIME REFERENCES TO HVDC FAULT LOCATION [J].
DEWE, MB ;
SANKAR, S ;
ARRILLAGA, J .
IEEE TRANSACTIONS ON POWER DELIVERY, 1993, 8 (03) :1295-1302
[9]   VSC-Based HVDC Power Transmission Systems: An Overview [J].
Flourentzou, Nikolas ;
Agelidis, Vassilios G. ;
Demetriades, Georgios D. .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2009, 24 (3-4) :592-602
[10]  
Lescale V., 2008, POWER SYSTEM TECHNOL, P1