Numerical study on performance of a desiccant cooling system with indirect evaporative cooler

被引:54
作者
Gao, Wenzhong [1 ]
Worek, William [2 ]
Konduru, Vinaykumar [2 ]
Adensin, Keith [2 ]
机构
[1] Shanghai Maritime Univ, Merchant Marine Coll, Shanghai 201306, Peoples R China
[2] Michigan Technol Univ, Dept Mech Engn Engn Mech, Houghton, MI 49931 USA
基金
中国国家自然科学基金;
关键词
Solid desiccant; Indirect evaporative cooler; NTU; Heat and mass transfer; MASS-TRANSFER; HEAT; OPTIMIZATION; SIMULATION;
D O I
10.1016/j.enbuild.2014.09.049
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Solid desiccant indirect evaporative cooling, driven by low-grade heat source, is an ideal alternative for conventional vapor compression systems to provide a thermal comfort condition in the humid area. Based on the coupled heat and mass transfer, the mathematical model, is developed to evaluate the performance of the hybrid system in terms of coefficient of performance (COP) and E-m. The sub-models were validated by comparing their results with the experimental results. The effects of the operating parameters, as well as the number of transfer units (NTU) on the performance of both heat exchanger and indirect evaporative cooler are numerically investigated. The results show that the optimum process inlet temperature and humidity should be less than 35 degrees C and 18 g/kg, respectively; E-m value is almost independent of the inlet air face velocity, regeneration air temperature, NTUHE and working air mass ratio; Increase in NTUHE or NTUIEC within a certain range (NTUHE <= 3, NTUIEC <= 6) both can improve the COP of the system; The working air mass ratio in indirect evaporative cooler can affect on the amount of air supplied to the room and the COP of the system, but almost can not affect the basic air conditions. (C) 2014 Elsevier B.V. All rights reserved.
引用
收藏
页码:16 / 24
页数:9
相关论文
共 16 条
[1]   Performance evaluation of an indirect evaporative cooler under controlled environmental conditions [J].
Ahmad, Aftab ;
Rehman, Shafiqur ;
Al-Hadhrami, Luai M. .
ENERGY AND BUILDINGS, 2013, 62 :278-285
[2]   PARAMETRIC STUDY OF AN OPEN-CYCLE ADIABATIC, SOLID, DESICCANT COOLING SYSTEM [J].
CHAROENSUPAYA, D ;
WOREK, WM .
ENERGY, 1988, 13 (09) :739-747
[3]   Energy performance of air-conditioning systems using an indirect evaporative, cooling combined with a cooling/reheating treatment [J].
Cianfrini, Claudio ;
Corcione, Massimo ;
Habib, Emanuele ;
Quintino, Alessandro .
ENERGY AND BUILDINGS, 2014, 69 :490-497
[4]   Indirect evaporative cooling: Past, present and future potentials [J].
Duan, Zhiyin ;
Zhan, Changhong ;
Zhang, Xingxing ;
Mustafa, Mahmud ;
Zhao, Xudong ;
Alimohammadisagvand, Behrang ;
Hasan, Ala .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2012, 16 (09) :6823-6850
[5]   Optimisation of a desiccant cooling system design with indirect evaporative cooler [J].
Goldsworthy, M. ;
White, S. .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2011, 34 (01) :148-158
[6]   Going below the wet-bulb temperature by indirect evaporative cooling: Analysis using a modified ε-NTU method [J].
Hasan, Ala .
APPLIED ENERGY, 2012, 89 (01) :237-245
[7]   OPTIMIZATION OF WET-SURFACE HEAT-EXCHANGERS [J].
HSU, ST ;
LAVAN, Z ;
WOREK, WM .
ENERGY, 1989, 14 (11) :757-770
[8]  
Jain S., 1996, FUEL EN ABSTR, V37, P286
[9]   HIGH-PERFORMANCE ADIABATIC DESICCANT OPEN-COOLING CYCLES [J].
MACLAINECROSS, IL .
JOURNAL OF SOLAR ENERGY ENGINEERING-TRANSACTIONS OF THE ASME, 1985, 107 (01) :102-104
[10]  
Pennington N., 1955, Patent No. USA patent, Patent No. [2, 700,537, 2700537]